Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 28, 2016, 11:19 AM
  • 01 1086_01 1085_20160128_031822.mp4

Date
01/28/2016
W/O
552639
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00210
PipeID
P01935
Time
3:19 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3129
Sewer Name
01 HUNTINGTON PARK TRUNK
City
SOUTH GATE, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_552639_TV01246_FEB2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Lining Method
Segmented Panel
Shape
Circular
Height
24 in.
Upstream MH
01 1086
Downstream MH
01 1085
Dir. of Survey
Downstream
Length Surveyed
217.8 ft.
Total Length
217.8 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2H00
O&M Rating
88
Overall Index
2
Overall Quick
Overall Rating
93
Pipe schematic from manhole 01 1086 to 01 1085
MH: 01 1086MH: 01 1085downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 10860 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start52.1 ft. DAR - Deposits Attached Ragging, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES73.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES214.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish217.8 ft. AMH - Downstream Manhole, Survey Ends - 01 1085

Observations (10)

DistanceCodeObservation
0MWL
214.6DAGS
0MWM
2DAGS
73.1CL
217.8AMH01 1085
1CM
52.1DAR
0AMH01 1086
0MGOLATERAL AT MH 3 OCLOCK

Properties (6)

additional_info
SC225516
custom_field_two
3
customer
LACSD
datetime
2016-01-28T03:19:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false