- Date
- 01/28/2016
- W/O
- 552639
- Weather
- Dry
- Operator/Surveyor
- J. HARTOOG
- Sewer ID
- Z00210
- PipeID
- P01932
- Time
- 2:45 AM
- Certificate
- U-507-03-3386
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K3129
- Sewer Name
- 01 HUNTINGTON PARK TRUNK
- City
- SOUTH GATE, CA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 08
- Purpose
- V
- Project
- RFIR_WO_552639_TV01246_FEB2016
- Sewer Type
- GRAVITY
- Material
- Vitrified Clay Pipe
- Lining Method
- Segmented Panel
- Shape
- Circular
- Height
- 24 in.
- Upstream MH
- 01 1082
- Downstream MH
- 01 1083
- Dir. of Survey
- Upstream
- Length Surveyed
- 249.6 ft.
- Total Length
- 249.6 ft.
- Structural Index
- 3
- Structural Quick
- 3300
- Structural Rating
- 9
- O&M Index
- 2
- O&M Quick
- 2I00
- O&M Rating
- 100
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 109
Pipe schematic from manhole 01 1082 to 01 1083 Observation photos (2)

243.3 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

249.6 ft. - Survey Abandoned - REVERSAL COMPLETE AT SAG