Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 11, 2016, 09:18 AM
  • 18 0479_18 0478_20160111_024915_.mp4

Date
01/11/2016
W/O
547052
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00691
PipeID
P14333
Time
1:18 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3031
Sewer Name
18 NORTH PLANT OUTFALL TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Routine Assessment
Project
RFIR_WO_547052_TV18140_JAN2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
18 0478
Downstream MH
18 0479
Dir. of Survey
Upstream
Length Surveyed
677.4 ft.
Total Length
677.4 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
3122
O&M Rating
10
Overall Index
2
Overall Quick
Overall Rating
13
Pipe schematic from manhole 18 0478 to 18 0479
MH: 18 0478MH: 18 0479upstream0 ft. MGO - General Observation - LATERAL AT MH 3 O'CLOCK ACTIVE0 ft. VC - Vermin Cockroach0 ft. AMH - Upstream Manhole, Survey Ends - 18 04790.4 ft. MGO - General Observation - MAGNESIUM H.O. FINISH2.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish154.1 ft. VC - Vermin Cockroach154.1 ft. TFD - Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: YES, 6" - ROOTS INSIDE337.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"347 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"403.6 ft. OBN - Obstacles Construction Debris, 15 %of cross sectional area, from 05 to 07 o'clock - NOT VISIBLE548.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"675.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start675.4 ft. MGO - General Observation - MAGNESIUM H.O. START675.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start677.4 ft. VC - Vermin Cockroach677.4 ft. AMH - Downstream Manhole, Survey Begins - 18 0478677.4 ft. MWL - Water Level, 15 %of cross sectional area677.4 ft. MGO - General Observation - LATERAL AT MH 9 O'CLOCK ACTIVE677.4 ft. MWM - Water Mark, 25 %of cross sectional area

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAGNESIUM H.O. START

    2 ft. - General Observation - MAGNESIUM H.O. START

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
0VC
273.8OBNNOT VISIBLE
2SAV
340TFC
2MGOMAGNESIUM H.O. START
330.4TBA
0AMH18 0478
523.3VC
677MGOMAGNESIUM H.O. FINISH
674.6SAV
0MWL
677.4MGOLATERAL AT MH 3 O'CLOCK ACTIVE
0MGOLATERAL AT MH 9 O'CLOCK ACTIVE
128.5TFA
677.4VC
674.5DAGS
0MWM
2DAGS
677.4AMH18 0479
523.3TFDROOTS INSIDE

Properties (6)

additional_info
SC224625
custom_field_two
3
customer
LACSD
datetime
2016-01-11T01:18:19-08:00
documentation
PRO PIPE
is_lateral_inspection
false