Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 25, 2016, 12:23 PM
  • F 0160_F 0153_20160125_045451.mp4

Date
01/25/2016
W/O
546989
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00043
PipeID
P10295
Time
4:23 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
k3166
Sewer Name
F JOINT OUTFALL F - UNIT 7A
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Routine Assessment
Project
RFIR_WO_546989_TV02202_JAN2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
51 in.
Upstream MH
F 0160
Downstream MH
F 0153
Dir. of Survey
Downstream
Length Surveyed
33.3 ft.
Total Length
33.3 ft.
Structural Index
5
Structural Quick
5100
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
5
Pipe schematic from manhole F 0160 to F 0153
MH: F 0160MH: F 0153downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - MAGNEZIUM H.O COATING 40% start0 ft. AMH - Upstream Manhole, Survey Begins - F 01600 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MGO - General Observation - SERVICE LATERAL AT 9 O'CLOCK AT MH2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start24.9 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish29.2 ft. MGO - General Observation - SERVICE LATERAL AT 9 O'CLOCK AT MH29.2 ft. MGO - General Observation - MAGNEZIUM H.O COATING 40% finish29.2 ft. MGO - General Observation - SERVICE LATERAL AT 3 O' CLOCK AT MH33.3 ft. AMH - Downstream Manhole, Survey Ends - F 0153

Observation photos (2)

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    24.9 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observations (11)

DistanceCodeObservation
0MWL
33.3AMHF 0153
0MGOMAGNEZIUM H.O COATING 40% start
0AMHF 0160
24.9SRC
0MWM
0MGOSERVICE LATERAL AT 9 O'CLOCK AT MH
2SRC
29.2MGOSERVICE LATERAL AT 9 O'CLOCK AT MH
29.2MGOMAGNEZIUM H.O COATING 40% finish
29.2MGOSERVICE LATERAL AT 3 O' CLOCK AT MH

Properties (7)

additional_info
SC224978
custom_field_two
2
customer
LACSD
datetime
2016-01-25T04:23:21-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
19930429