Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 13, 2016, 07:32 AM
  • 02 1550_02 1549_20160113_002100_.mp4

Date
01/12/2016
W/O
544149
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00230
PipeID
P03982
Time
11:32 PM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2954
Sewer Name
02 ARIZONA AVENUE TRUNK, SECTION 1
City
LOS ANGELES
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_544149_TV02006_JAN2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 1550
Downstream MH
02 1549
Dir. of Survey
Downstream
Length Surveyed
311.7 ft.
Total Length
311.7 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
165
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
167
Pipe schematic from manhole 02 1550 to 02 1549
MH: 02 1550MH: 02 1549downstream0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK0 ft. VC - Vermin Cockroach0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 155029.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start41.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"56.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"77.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"79.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"103.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"126.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"129 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"154.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"175.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"178 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"206.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"226.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"229.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"257.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"280.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"283.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"306.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish311.6 ft. VC - Vermin Cockroach311.6 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK311.7 ft. AMH - Downstream Manhole, Survey Ends - 02 1549

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    29.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (26)

DistanceCodeObservation
311.7AMH02 1549
306.2CM
0MGOLATERAL AT MH 9 OCLOCK
29.4CM
311.6VC
129TF
0VC
257.6TF
0MWL
229.4TF
283.4TF
206.2TFA
41.2TFA
0MWM
126.6TFC
311.6MGOLATERAL AT MH 9 OCLOCK
77.2TF
178TFC
154.8TFC
280.6TFC
79.8TFC
103.4TF
0AMH02 1550
175.3TFA
56.5TF
226.8TFC

Properties (6)

additional_info
SC224965
custom_field_two
3
customer
LACSD
datetime
2016-01-12T23:32:41-08:00
documentation
PRO PIPE
is_lateral_inspection
false