Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 25, 2017, 07:29 AM
  • A 0307_A 0306_5252017_011826.mp4

Date
05/25/2017
W/O
0640849
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00325
PipeID
P08217
Time
12:29 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0535
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
20170525MDM_JOA_1A_SAN_JOSE_CREEK_WRP_INTERCEPTOR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
63 in.
Upstream MH
A 0307
Downstream MH
A 0306
Dir. of Survey
Downstream
Length Surveyed
216.9 ft.
Total Length
216.9 ft.
Structural Index
3
Structural Quick
5132
Structural Rating
13
O&M Index
5
O&M Quick
5241
O&M Rating
14
Overall Index
4
Overall Quick
Overall Rating
27
Pipe schematic from manhole A 0307 to A 0306
MH: A 0307MH: A 0306downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:10AM2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING,FLAKING CONCRETE8 ft. MGO - General Observation - PEELING MASTIC AT JOINTS START19.3 ft. MGO - General Observation - PEELING MASTIC AT JOINTS25.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC32.7 ft. MGO - General Observation - HANGING MASTIC128.2 ft. MGO - General Observation - PEELING HANGING MASTIC136.3 ft. MWM - Water Mark, 80 %of cross sectional area146.2 ft. MGO - General Observation - PEELING HANGING MASTIC157.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG157.5 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG184 ft. MWM - Water Mark, 90 %of cross sectional area184 ft. MWL - Water Level, 70 %of cross sectional area202.7 ft. MGO - General Observation - HANGING MASTIC206.3 ft. MGO - General Observation - ZOOM 10'216.3 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR216.3 ft. MGP - General Photograph - CIRCUM REBAR AT 12:00216.3 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG216.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING ,FLAKING CONCRETE216.3 ft. MGO - General Observation - PEELING MASTIC AT JOINTS FINISH216.9 ft. MSA - Survey Abandoned - DOWNLEG UPSTREAM SIPHON

Observation photos (13)

  • General Observation - PEELING MASTIC AT JOINTS START

    8 ft. - General Observation - PEELING MASTIC AT JOINTS START

  • General Observation - PEELING MASTIC AT JOINTS

    19.3 ft. - General Observation - PEELING MASTIC AT JOINTS

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    25.2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • General Observation - HANGING MASTIC

    32.7 ft. - General Observation - HANGING MASTIC

  • General Observation - PEELING HANGING MASTIC

    128.2 ft. - General Observation - PEELING HANGING MASTIC

  • Water Mark, 80 %of cross sectional area

    136.3 ft. - Water Mark, 80 %of cross sectional area

  • General Observation - PEELING HANGING MASTIC

    146.2 ft. - General Observation - PEELING HANGING MASTIC

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    157.5 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Water Mark, 90 %of cross sectional area

    184 ft. - Water Mark, 90 %of cross sectional area

  • General Observation - HANGING MASTIC

    202.7 ft. - General Observation - HANGING MASTIC

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    216.3 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • General Photograph - CIRCUM REBAR AT 12:00

    216.3 ft. - General Photograph - CIRCUM REBAR AT 12:00

  • Survey Abandoned - DOWNLEG UPSTREAM SIPHON

    216.9 ft. - Survey Abandoned - DOWNLEG UPSTREAM SIPHON

Observations (23)

DistanceCodeObservation
25.2SAVSEVERE AGG SPORATIC
216.3SRVCIRCUM REBAR
184MWM
32.7MGOHANGING MASTIC
2SSSBLISTERING,FLAKING CONCRETE
216.3MGPCIRCUM REBAR AT 12:00
128.2MGOPEELING HANGING MASTIC
8MGOPEELING MASTIC AT JOINTS START
19.3MGOPEELING MASTIC AT JOINTS
136.3MWM
216.9MSADOWNLEG UPSTREAM SIPHON
202.7MGOHANGING MASTIC
206.3MGOZOOM 10'
216.3SAPSEVERE AGG
0MWL
184MWL
216.3SSSBLISTERING ,FLAKING CONCRETE
216.3MGOPEELING MASTIC AT JOINTS FINISH
0MWM
157.5SAPSEVERE AGG
146.2MGOPEELING HANGING MASTIC
157.5SAVSEVERE AGG
0AMH1:10AM

Properties (8)

additional_info
DOWMLEG UPSTREAM SIPHON
custom_field_three
ONE AREA CIRCUM REBAR,SEVERE AGG PROJECTNG
custom_field_two
3
customer
LACSD
datetime
2017-05-25T00:29:32-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false
year_laid
19790427