Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 23, 2017, 04:00 PM
  • A 0328_A 0327_5232017_092547.mp4

Date
05/23/2017
W/O
0640653
Weather
Dry
Operator/Surveyor
IGNACIO
Sewer ID
Z00325
PipeID
P08238
Time
9:00 AM
Certificate
PENDING
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7413
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
22
Purpose
Capital Improvement Program Assesment
Project
20170523MI_JOA_1A_SAN_JOSE_CREEK_WRP_INTERCEPTOR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Upstream MH
A 0328
Downstream MH
A 0327
Dir. of Survey
Downstream
Length Surveyed
2.5 ft.
Total Length
2.5 ft.
Structural Index
3
Structural Quick
3221
Structural Rating
8
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
12
Pipe schematic from manhole A 0328 to A 0327
MH: A 0328MH: A 0327downstream0 ft. MGO - General Observation - AIRLINE AT MH, 12 OCLOCK0 ft. MWL - Water Level, 100 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 09:30 AM2 ft. LD - Alignment Down, 45 %2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES2.3 ft. SAVC - Surface Aggregate Visible Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES2.4 ft. SRP - Surface Reinforcement Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES2.5 ft. MGO - General Observation - VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON2.5 ft. MSA - Survey Abandoned - VIEW OF DOWNLEG PIPE OF THE U/S SIPHON

Observation photos (4)

  • General Observation - AIRLINE AT MH, 12 OCLOCK

    0 ft. - General Observation - AIRLINE AT MH, 12 OCLOCK

  • Surface Aggregate Visible Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.3 ft. - Surface Aggregate Visible Chemical, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.4 ft. - Surface Reinforcement Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

  • General Observation - VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON

    2.5 ft. - General Observation - VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON

Observations (9)

DistanceCodeObservation
0MGOAIRLINE AT MH, 12 OCLOCK
2.3SAVC
2.5MGOVIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON
0MWL
2LD
0AMH09:30 AM
2.5MSAVIEW OF DOWNLEG PIPE OF THE U/S SIPHON
2.4SRP
2SSS

Properties (7)

additional_info
VIEW OF DOWNLEG PIPE OF THE U/S SIPHON
custom_field_two
2
customer
LACSD
datetime
2017-05-23T09:00:55-07:00
documentation
IGNACIO, FRANKLIN, OBREGON
is_lateral_inspection
false
year_laid
19800403