Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 8, 2016, 12:16 PM
  • 19 0057_19 0056_20160308_053323.mp4

Date
03/08/2016
W/O
557873
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00724
PipeID
P15088
Time
4:16 AM
Certificate
U507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3218
Sewer Name
19 ELAINE AVENUE TRUNK
City
LAKEWOOD, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
06
Purpose
V
Project
WO_557873_TV19004_2016MAR
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
19 0056
Downstream MH
19 0057
Dir. of Survey
Upstream
Length Surveyed
242.5 ft.
Total Length
242.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 19 0056 to 19 0057
MH: 19 0056MH: 19 0057upstream0 ft. MSA - Survey Abandoned - REVERSAL COMPLETE0 ft. MGO - General Observation - REVERSAL COMPLETE AT DEBRIS0 ft. DNGV - Deposits Ingress Gravel, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES7 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 4" - CALCIUM11.2 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 4" - CALCIUM46.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 12 to 03 o'clock, , within 8 inches of joint: YES59.2 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"62.1 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"110.7 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"115.4 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"155.2 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4" - CALCIUM194.8 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"198.6 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"214.4 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"242.5 ft. MGO - Reversal Inspection242.5 ft. AMH - Downstream Manhole, Survey Begins - 19 0056242.5 ft. MWL - Water Level, 15 %of cross sectional area242.5 ft. MWM - Water Mark, 20 %of cross sectional area

Observation photos (2)

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4" - CALCIUM

    87.3 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4" - CALCIUM

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 12 to 03 o'clock,  , within 8 inches of joint: YES

    195.8 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 12 to 03 o'clock, , within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
87.3TBACALCIUM
43.9TBA
235.5TBACALCIUM
47.7TBC
0MGO
0AMH19 0056
180.4TBA
231.3TBCALCIUM
127.1TBA
0MWL
195.8DAE
131.8TBA
183.3TBA
28.1TBA
242.5MSAREVERSAL COMPLETE
242.5MGOREVERSAL COMPLETE AT DEBRIS
242.5DNGV
0MWM

Properties (6)

additional_info
SC305308
custom_field_two
4
customer
LACSD
datetime
2016-03-08T04:16:38-08:00
documentation
PRO-PIPE
is_lateral_inspection
false