Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 10, 2016, 12:04 PM
  • 19 0044_19 0036_20160310_052353.mp4

Date
03/10/2016
W/O
557873
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00724
PipeID
P15074
Time
4:04 AM
Certificate
U507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3221
Sewer Name
19 ELAINE AVENUE TRUNK
City
LAKEWOOD, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
09
Purpose
Routine Assessment
Project
WO_557873_TV19004_2016MAR
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
19 0044
Downstream MH
19 0036
Dir. of Survey
Downstream
Length Surveyed
388.8 ft.
Total Length
388.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2^00
O&M Rating
310
Overall Index
2
Overall Quick
Overall Rating
310
Pipe schematic from manhole 19 0044 to 19 0036
MH: 19 0044MH: 19 0036downstream0 ft. AMH - Upstream Manhole, Survey Begins - 19 00440 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - CAPPED LATERAL 3 O'CLOCK @ MH0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CAPPED LATERAL 9 O'CLOCK @ MH4.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start4.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start12.3 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"16.7 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"64.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"68.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"113.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"117.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"165.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"169.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"213.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"217.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"262.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"266.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"306 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"309.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"354.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"358.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"385.3 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish388.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish388.8 ft. MGO - General Observation - LATERAL AT MH 12 OCLOCK388.8 ft. AMH - Downstream Manhole, Survey Ends - 19 0036388.8 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    4.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (28)

DistanceCodeObservation
0AMH19 0044
117.4TFC
388.8MGOLATERAL AT MH 12 OCLOCK
64.3TFC
4.7DAE
358.5TFC
306TFC
262.2TFC
388.8AMH19 0036
385.3DAE
0MWM
388.5DAGS
0MGOCAPPED LATERAL 3 O'CLOCK @ MH
68.4TFC
16.7TBC
165.1TFC
388.8MGOLATERAL AT MH 9 OCLOCK
169.4TFC
0MWL
213.8TFC
12.3TBC
4.7DAGS
309.8TFC
266.4TFC
354.9TFC
113.1TFC
0MGOCAPPED LATERAL 9 O'CLOCK @ MH
217.3TFC

Properties (6)

additional_info
SC305311
custom_field_two
4
customer
LACSD
datetime
2016-03-10T04:04:58-08:00
documentation
PRO-PIPE
is_lateral_inspection
false