Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 23, 2016, 09:00 AM
  • 18 0375_18 0374_20160323_021856.mp4

Date
03/23/2016
W/O
557580
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00690
PipeID
P14209
Time
2:00 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3233
Sewer Name
18 NORTH NORWALK TRUNK
City
NORWALK, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
25
Purpose
Routine Assessment
Project
RFIR_WO_557580_TV18095_2016MAR
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
18 0375
Downstream MH
18 0374
Dir. of Survey
Downstream
Length Surveyed
348.6 ft.
Total Length
348.6 ft.
Structural Index
4
Structural Quick
4131
Structural Rating
7
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 18 0375 to 18 0374
MH: 18 0375MH: 18 0374downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 03750 ft. MWL - Water Level, 10 %of cross sectional area7.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - WANDERING7.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start41.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 4"70.6 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"120.7 ft. MGP - General Photograph142.1 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 4" - W/ HEAVY GREASE242 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"329.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish329.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start345.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish345.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish348.6 ft. MGO - General Observation - CAPPED LATERAL AT MH 9 & 3 OCLOCK348.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0374348.6 ft. VC - Vermin Cockroach

Observation photos (6)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - WANDERING

    7.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - WANDERING

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    7.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    70.6 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • General Photograph

    120.7 ft. - General Photograph

  • Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 4" - W/ HEAVY GREASE

    142.1 ft. - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 4" - W/ HEAVY GREASE

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    329.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
329.8CM
348.6MGOCAPPED LATERAL AT MH 9 & 3 OCLOCK
120.7MGP
0MWM
348.6AMH18 0374
348.6VC
345.2FM
242TFC
0AMH18 0375
0MWL
329.8FM
7.1CMWANDERING
142.1TFAW/ HEAVY GREASE
70.6TBA
7.1DAGS
41.3TF
345.2DAGS

Properties (6)

additional_info
SC305324
custom_field_two
3
customer
LACSD
datetime
2016-03-23T02:00:52-07:00
documentation
PRO-PIPE
is_lateral_inspection
false