Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 24, 2017, 09:04 AM
  • 18 0373_18 0372_5242017_023513.mp4

Date
05/24/2017
W/O
0630165
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00690
PipeID
P14207
Time
2:04 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0534
Sewer Name
18 NORTH NORWALK TRUNK
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
25
Purpose
Capital Improvement Program Assesment
Project
20170522MDM_NORTH_NORWALK_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
18 0373
Downstream MH
18 0372
Dir. of Survey
Downstream
Length Surveyed
349.8 ft.
Total Length
349.8 ft.
Structural Index
2
Structural Quick
342A
Structural Rating
34
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
39
Pipe schematic from manhole 18 0373 to 18 0372
MH: 18 0373MH: 18 0372downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 3:35AM0.1 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SLIGHT10.2 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - HAIRLINE10.2 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SL14.3 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - H14.3 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL18.6 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL18.6 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL22.5 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL22.5 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H26.5 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL26.5 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL30.7 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS30.7 ft. FL - Fracture Longitudinal, at 08 TO 4 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS30.7 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS30.7 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS30.7 ft. MGO - General Observation - 15" VCP96.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES96.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active194.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active194.4 ft. DAGS - Deposits Attached Grease, 20 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES297.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped349.4 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 30% HAIRLINE AT JOINTS349.4 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 80% SLIGHT AT JOINTS349.4 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 30% SLIGHT AT JOINTS349.4 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 50% HAIRLINE AT JOINTS349.4 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active349.8 ft. AMH - Downstream Manhole, Survey Ends - 3:20AM

Observation photos (1)

  • Deposits Attached Grease, 20 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    194.4 ft. - Deposits Attached Grease, 20 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

Observations (31)

DistanceCodeObservation
0.1FCSLIGHT
30.7FCHAIRLINE AT JOINTS
18.6FCSL
96.7DAGS
349.4FL30% HAIRLINE AT JOINTS
14.3FCH
0MWM
30.7FLHAIRLINE AT JOINTS
194.4TFActive
349.4FC80% SLIGHT AT JOINTS
349.4FL30% SLIGHT AT JOINTS
10.2FLHAIRLINE
0MWL
297.8TFCCapped
18.6FCSL
0MGOConn. @ Mh, 9 O' Clock. Active
349.4FC50% HAIRLINE AT JOINTS
26.5FCSL
194.4DAGS
14.3FCSL
30.7FCSLIGHT AT JOINTS
22.5FCSL
0AMH3:35AM
30.7FLSLIGHT AT JOINTS
349.4MGOConn. @ Mh, 9 O' Clock. Active
30.7MGO15" VCP
22.5FCH
349.8AMH3:20AM
10.2FLSL
26.5FCSL
96.7TFActive

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2017-05-24T02:04:20-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false