Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 18, 2017, 03:49 PM
  • A 0537_A 0536_5182017_092611.mp4

Date
05/18/2017
W/O
0618889
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00315
PipeID
P07774
Time
8:49 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7407
Sewer Name
A JOA-1A DISTRICT 5 INTERCEPTOR
City
LAWNDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
20170518DF_JOA_1A_DISTRICT_5_INTERCEPTOR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
A 0536
Downstream MH
A 0537
Dir. of Survey
Upstream
Length Surveyed
363.9 ft.
Total Length
363.9 ft.
Structural Index
4
Structural Quick
5231
Structural Rating
15
O&M Index
3
O&M Quick
3221
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
23
Pipe schematic from manhole A 0536 to A 0537
MH: A 0536MH: A 0537upstream0 ft. AMH - Upstream Manhole, Survey Ends - 9:59 AM1.2 ft. DAR - Deposits Attached Ragging, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish1.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.2 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish1.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish61.8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start108.1 ft. MGP - General Photograph - AGGREGATE/SPALLING112.7 ft. DAGS - Deposits Attached Grease, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES134.9 ft. SRV - Surface Reinforcement Visible, from 09 to 01 o'clock, within 8 inches of joint: YES172.3 ft. MGP - General Photograph - GREASE193.1 ft. MGP - General Photograph302.3 ft. MGP - General Photograph - SPALLING361.9 ft. DAR - Deposits Attached Ragging, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start361.9 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start361.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start361.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start363.8 ft. MWL - Water Level, 5 %of cross sectional area363.8 ft. MWM - Water Mark, 10 %of cross sectional area363.9 ft. AMH - Downstream Manhole, Survey Begins - 8:54 AM

Observation photos (11)

  • Deposits Attached Ragging, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Ragging, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 15 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph - SPALLING

    61.6 ft. - General Photograph - SPALLING

  • General Photograph

    170.8 ft. - General Photograph

  • General Photograph - GREASE

    191.6 ft. - General Photograph - GREASE

  • Surface Reinforcement Visible, from 09 to 01 o'clock, within 8 inches of joint: YES

    229 ft. - Surface Reinforcement Visible, from 09 to 01 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 20 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES

    251.2 ft. - Deposits Attached Grease, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES

  • General Photograph - AGGREGATE/SPALLING

    255.8 ft. - General Photograph - AGGREGATE/SPALLING

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    302.1 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
61.6MGPSPALLING
2DAR
362.7DAR
362.7SAV
302.1SRC
0.1MWL
362.7SSS
191.6MGPGREASE
0AMH8:54 AM
2DAGS
0.1MWM
255.8MGPAGGREGATE/SPALLING
2SSS
2SAV
170.8MGP
229SRV
251.2DAGS
363.9AMH9:59 AM
362.7DAGS
362.7SRC

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2017-05-18T08:49:30-07:00
documentation
FRANKLIN, IGNACIO, BRAR
is_lateral_inspection
false