Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 26, 2016, 06:12 AM
  • A 1264_A 1263_20160125_233908_.mp4

Date
01/25/2016
W/O
536343
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00316
PipeID
P24612
Time
10:12 PM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3167
Sewer Name
A JOA-1A DISTRICT 21 INTERCEPTOR
City
CITY OF INDUSTRY
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
28
Purpose
Routine Assessment
Project
WO_536343_TV21083_NOV2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
39 in.
Upstream MH
A 1264
Downstream MH
A 1263
Dir. of Survey
Downstream
Length Surveyed
434.5 ft.
Total Length
434.5 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole A 1264 to A 1263
MH: A 1264MH: A 1263downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 1264163 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES238.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 10"434.5 ft. AMH - Downstream Manhole, Survey Ends - A 1263

Observation photos (1)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    163 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (6)

DistanceCodeObservation
0MWM
238.5TFC
163CL
434.5AMHA 1263
0MWL
0AMHA 1264

Properties (7)

additional_info
SC224979
custom_field_two
4
customer
LACSD
datetime
2016-01-25T22:12:21-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
20011212