Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 17, 2015, 10:00 AM
  • 01 0124_01 0123_17122015_020124.mp4

Date
12/17/2015
W/O
524985
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00204
PipeID
P02068
Time
2:00 AM
Certificate
12345
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2964
Sewer Name
01 COMPTON CREEK EXTENSION TRUNK, SECTION 2
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
15
Purpose
Routine Assessment
Project
WO_524985_TV011104_NOV2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Lining Method
Segmented Panel
Shape
Circular
Height
18 in.
Upstream MH
01 0123
Downstream MH
01 0124
Dir. of Survey
Upstream
Length Surveyed
42.9 ft.
Total Length
42.9 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
3
O&M Quick
4137
O&M Rating
25
Overall Index
3
Overall Quick
Overall Rating
27
Pipe schematic from manhole 01 0123 to 01 0124
MH: 01 0123MH: 01 0124upstream0 ft. MGO - General Observation - MAGNEZIUM H.O. FINISH0 ft. MSA - Survey Abandoned - REVERSE INSPECTION COMPLETE MATED FOOTAGE0 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish35.8 ft. CS - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES35.8 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start35.8 ft. MGO - General Observation - MAGNEZIUM H.O. START42.9 ft. MWL - Water Level, 40 %of cross sectional area42.9 ft. MWM - Water Mark, 60 %of cross sectional area42.9 ft. AMH - Downstream Manhole, Survey Begins - 01 0123

Observation photos (3)

  • Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES

    7.1 ft. - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    7.1 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Survey Abandoned - REVERSE INSPECTION COMPLETE MATED FOOTAGE

    42.9 ft. - Survey Abandoned - REVERSE INSPECTION COMPLETE MATED FOOTAGE

Observations (9)

DistanceCodeObservation
0MWL
7.1CS
7.1DAGS
0MWM
0AMH01 0123
42.9MGOMAGNEZIUM H.O. FINISH
42.9MSAREVERSE INSPECTION COMPLETE MATED FOOTAGE
7.1MGOMAGNEZIUM H.O. START
42.9DAGS

Properties (6)

additional_info
SC224803
custom_field_two
3
customer
LACSD
datetime
2015-12-17T02:00:33-08:00
documentation
PRO PIPE
is_lateral_inspection
false