Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 10, 2015, 08:24 AM
  • 01 0150_01 0149_10122015_002550.mp4

Date
12/10/2015
W/O
524985
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00204
PipeID
P02093
Time
12:24 AM
Certificate
12345
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2960
Sewer Name
01 COMPTON CREEK EXTENSION TRUNK, SECTION 2
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
WO_524985_TV011104_NOV2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Lining Method
Segmented Panel
Shape
Circular
Height
15 in.
Upstream MH
01 0150
Downstream MH
01 0149
Dir. of Survey
Downstream
Length Surveyed
280.3 ft.
Total Length
280.3 ft.
Structural Index
2
Structural Quick
332A
Structural Rating
33
O&M Index
4
O&M Quick
4J00
O&M Rating
224
Overall Index
4
Overall Quick
Overall Rating
257
Pipe schematic from manhole 01 0150 to 01 0149
MH: 01 0150MH: 01 0149downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 01500 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area3.8 ft. DAGS - Deposits Attached Grease, 30 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start17 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES22.8 ft. CS - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES38.1 ft. CM - Crack Multiple, from 06 to 11 o'clock, within 8 inches of joint: YES52.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES63.3 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES74.5 ft. CM - Crack Multiple, from 06 to 12 o'clock, within 8 inches of joint: YES78.1 ft. CS - Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES98.8 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES114 ft. CS - Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES123.5 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES128.7 ft. CS - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES164.4 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES166 ft. CM - Crack Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES170.4 ft. CS - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES201.2 ft. CS - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES278.1 ft. DAGS - Deposits Attached Grease, 30 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish280.3 ft. AMH - Downstream Manhole, Survey Ends - 01 0149

Observation photos (16)

  • Deposits Attached Grease, 30 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    3.8 ft. - Deposits Attached Grease, 30 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    17 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

    22.8 ft. - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 06 to 11 o'clock, within 8 inches of joint: YES

    38.1 ft. - Crack Multiple, from 06 to 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    52.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    63.3 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 06 to 12 o'clock, within 8 inches of joint: YES

    74.5 ft. - Crack Multiple, from 06 to 12 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES

    78.1 ft. - Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    98.8 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES

    114 ft. - Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    123.5 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

    128.7 ft. - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    164.4 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES

    166 ft. - Crack Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

    170.4 ft. - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

    201.2 ft. - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
170.4CS
280.3AMH01 0149
201.2CS
3.8DAGS
17CL
114CS
0AMH01 0150
38.1CM
128.7CS
278.1DAGS
78.1CS
166CM
63.3CL
0MWL
22.8CS
164.4CL
0MWM
98.8CL
74.5CM
52.8CL
123.5CL

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-12-10T00:24:28-08:00
documentation
PRO PIPE
is_lateral_inspection
false