01 0141_01 0140_15122015_032807.mp4

2.1 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

22.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

58.1 ft. - Crack Spiral, from 12 to 05 o'clock, within 8 inches of joint: YES

67.4 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

97.9 ft. - Crack Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES

109 ft. - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

119.8 ft. - Fracture Spiral, from 07 to 12 o'clock, within 8 inches of joint: YES
| Distance | Code | Observation |
|---|---|---|
| 0 | MWL | — |
| 0 | MWM | — |
| 123.7 | DAGS | — |
| 124.1 | AMH | 01 0140 |
| 2.1 | DAGS | — |
| 58.1 | CS | — |
| 0 | AMH | 01 0141 |
| 22.9 | CM | — |
| 109 | CM | — |
| 97.9 | CS | — |
| 67.4 | CL | — |
| 119.8 | FS | — |