Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 11, 2017, 06:18 AM
  • 01 1369_01 0795_10042017_232141.mp4

Date
04/10/2017
W/O
630043
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00197
PipeID
P01498
Time
11:18 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4424
Sewer Name
01 BULLIS ROAD-TEMPLE STREET TRUNK
City
LYNWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Routine Assessment
Project
WO_630043_TV01008_APR2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 1369
Downstream MH
01 0795
Dir. of Survey
Downstream
Length Surveyed
135.8 ft.
Total Length
135.8 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
78
O&M Index
2
O&M Quick
412D
O&M Rating
56
Overall Index
3
Overall Quick
Overall Rating
134
Pipe schematic from manhole 01 1369 to 01 0795
MH: 01 1369MH: 01 0795downstream0 ft. MWM - Water Mark, 65 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 13690 ft. MWL - Water Level, 50 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start5.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start8.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"57.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"81.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"129.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"134.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish134.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Finish135.8 ft. AMH - Downstream Manhole, Survey Ends - 01 0795

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    5.5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
134.2FL
81.4TFC
8.5TFC
57.9TFC
0MWM
0AMH01 1369
5.5FL
2DAGS
129.9TFC
134.2DAGS
0MWL
135.8AMH01 0795

Properties (6)

additional_info
SC306993
custom_field_two
3
customer
LACSD
datetime
2017-04-10T23:18:04-07:00
documentation
PRO PIPE
is_lateral_inspection
false