Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 12, 2017, 07:04 AM
  • 01 1367_01 1366_12042017_000522.mp4

Date
04/12/2017
W/O
630043
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00197
PipeID
P21397
Time
12:04 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4425
Sewer Name
01 BULLIS ROAD-TEMPLE STREET TRUNK
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Routine Assessment
Project
WO_630043_TV01008_APR2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
01 1367
Downstream MH
01 1366
Dir. of Survey
Downstream
Length Surveyed
360.5 ft.
Total Length
360.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2M00
O&M Rating
144
Overall Index
2
Overall Quick
Overall Rating
144
Pipe schematic from manhole 01 1367 to 01 1366
MH: 01 1367MH: 01 1366downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 13670 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start81 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"130.7 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"351.2 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - DEBRIS359.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish360.5 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK360.5 ft. AMH - Downstream Manhole, Survey Ends - 01 1366360.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    360.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (12)

DistanceCodeObservation
360.5MGOACTIVE CONNECTION AT MH 3 O'CLOCK
360.5AMH01 1366
359.4DAGS
351.2DSZDEBRIS
360.5MGOCOCKROACHES IN MANHOLE
130.7TFA
0MWL
0MWM
2DAGS
81TFA
0AMH01 1367
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK

Properties (7)

additional_info
SC306994
custom_field_two
4
customer
LACSD
datetime
2017-04-12T00:04:39-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
35417