Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 20, 2017, 09:42 AM
  • 01 1382_01 1381_20042017_024334.mp4

Date
04/20/2017
W/O
630043
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00197
PipeID
P22187
Time
2:42 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4435
Sewer Name
01 BULLIS ROAD-TEMPLE STREET TRUNK
City
LYNWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
14
Purpose
Routine Assessment
Project
WO_630043_TV01008_APR2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
01 1382
Downstream MH
01 1381
Dir. of Survey
Downstream
Length Surveyed
285.6 ft.
Total Length
285.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 01 1382 to 01 1381
MH: 01 1382MH: 01 1381downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 13820 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start27.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"145.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"261.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"284 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish285.6 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK285.6 ft. AMH - Downstream Manhole, Survey Ends - 01 1381

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
145.1TFC
285.6MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0MWM
284DAGS
0AMH01 1382
261.1TF
2DAGS
0MWL
27.9TFA
285.6AMH01 1381

Properties (7)

additional_info
SC345207
custom_field_two
4
customer
LACSD
datetime
2017-04-20T02:42:42-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
35934