Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 11, 2017, 10:59 AM
  • 01 1350_01 1349_11042017_035929.mp4

Date
04/11/2017
W/O
630043
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00197
PipeID
P20016
Time
3:59 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4424
Sewer Name
01 BULLIS ROAD-TEMPLE STREET TRUNK
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Routine Assessment
Project
WO_630043_TV01008_APR2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
01 1349
Downstream MH
01 1350
Dir. of Survey
Upstream
Length Surveyed
22 ft.
Total Length
22 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
4124
O&M Rating
12
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole 01 1349 to 01 1350
MH: 01 1349MH: 01 1350upstream0 ft. AMH - Upstream Manhole, Survey Ends - 01 13501.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish20 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start22 ft. MWL - Water Level, 20 %of cross sectional area22 ft. MWM - Water Mark, 50 %of cross sectional area22 ft. AMH - Downstream Manhole, Survey Begins - 01 1349

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (6)

DistanceCodeObservation
0MWL
0MWM
22AMH01 1350
2DAGS
0AMH01 1349
20.8DAGS

Properties (6)

additional_info
SC306993
custom_field_two
4
customer
LACSD
datetime
2017-04-11T03:59:07-07:00
documentation
PRO PIPE
is_lateral_inspection
false