Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 6, 2017, 05:23 PM
  • 01 0109_01 0108_762017_105038.mp4

Date
07/06/2017
W/O
PENDING
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00203
PipeID
P01173
Time
10:23 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7455
Sewer Name
01 COMPTON CREEK EXTENSION TRUNK, SECTION 1
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
15
Purpose
Maintenance Related
Project
20170706DF_COMPTON_CREEK_EXT_TR_SEC_1
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
01 0109
Downstream MH
01 0108
Dir. of Survey
Downstream
Length Surveyed
135.5 ft.
Total Length
135.5 ft.
Structural Index
2
Structural Quick
3321
Structural Rating
12
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole 01 0109 to 01 0108
MH: 01 0109MH: 01 0108downstream0 ft. AMH - Upstream Manhole, Survey Begins - 10:26 AM0 ft. MWL - Water Level, 40 %of cross sectional area0.1 ft. MWM - Water Mark, 45 %of cross sectional area2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start37.2 ft. CC - Crack Circumferential, from 09 to 04 o'clock, within 8 inches of joint: YES38.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"40.1 ft. CM - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES76.9 ft. CM - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES119 ft. MGP - General Photograph135.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish135.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish135.5 ft. MSA - Survey Abandoned - CAMERA FLIPPED

Observation photos (6)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Circumferential, from 09 to 04 o'clock, within 8 inches of joint: YES

    37.2 ft. - Crack Circumferential, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

    40.1 ft. - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

    76.9 ft. - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

  • General Photograph

    119 ft. - General Photograph

Observations (13)

DistanceCodeObservation
0.1MWM
0AMH10:26 AM
2CM
2SSS
40.1CM
76.9CM
135.5SSS
37.2CC
0MWL
135.5CM
135.5MSACAMERA FLIPPED
119MGP
38.2TFC

Properties (6)

additional_info
GREASE INSPECTION
custom_field_two
5
customer
LACSD
datetime
2017-07-06T10:23:25-07:00
documentation
FRANKLIN, IGNACIO, BRAR
is_lateral_inspection
false