Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 5, 2017, 08:47 AM
  • Section#3_F 0158_F 0157__752017__G6775.mp4

Date
07/05/2017
W/O
0649649
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00043
PipeID
P10292
Time
1:47 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6775
Sewer Name
F JOINT OUTFALL F - UNIT 7A
City
CERRITOS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Routine Assessment
Project
20170705MDM_JOINT_OUTFALL_F_UNIT_7A
Material
Reinforced Concrete Pipe
Shape
Circular
Height
51 in.
Upstream MH
F 0158
Downstream MH
F 0157
Dir. of Survey
Downstream
Length Surveyed
452.9 ft.
Total Length
452.9 ft.
Structural Index
4
Structural Quick
584Q
Structural Rating
402
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
402
Pipe schematic from manhole F 0158 to F 0157
MH: F 0158MH: F 0157downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:50AM2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. MGO - General Observation - MAG COAT 70% START 8:00 TO 4:0012.4 ft. MGO - General Observation - MAG COAT 60%44.9 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR52.8 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR59.6 ft. SRV - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: YES - CIRCUM REBAR154.6 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR285.9 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: YES - CIRCUM REBAR348.3 ft. SRV - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR385.7 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR391.4 ft. SRV - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR437.3 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - CIRCUM REBAR452.4 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG452.4 ft. MGO - General Observation - MAG COAT 70% FINISH452.9 ft. AMH - Downstream Manhole, Survey Ends - 4:35AM

Observation photos (12)

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - MAG COAT 70% START 8:00 TO 4:00

    2 ft. - General Observation - MAG COAT 70% START 8:00 TO 4:00

  • General Observation - MAG COAT 60%

    12.4 ft. - General Observation - MAG COAT 60%

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    44.9 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    52.8 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    59.6 ft. - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    154.6 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    285.9 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    348.3 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    385.7 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    391.4 ft. - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    437.3 ft. - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

Observations (18)

DistanceCodeObservation
12.4MGOMAG COAT 60%
44.9SRVCIRCUM REBAR
0MWL
2SAMSEVERE AGG
437.3FCCIRCUM REBAR
2MGOMAG COAT 70% START 8:00 TO 4:00
452.4SAMSEVERE AGG
385.7SRVCIRCUM REBAR
285.9SRVCIRCUM REBAR
452.9AMH4:35AM
154.6SRCCIRCUM REBAR
0MWM
348.3SRVCIRCUM REBAR
452.4MGOMAG COAT 70% FINISH
0AMH3:50AM
52.8SRVCIRCUM REBAR
59.6SRVCIRCUM REBAR
391.4SRVCIRCUM REBAR

Properties (5)

custom_field_two
CIRCUM REBAR VISIBLE
customer
LACSD
datetime
2017-07-05T01:47:16-07:00
documentation
MARTIN,MANANES,REVELES,LIVER 111
is_lateral_inspection
false