Section#1_F 0153_F 0159__752017__G6775.mp4
2 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR
2 ft. - General Observation - MAG COAT 10% START 8:00 TO 4:00
2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG
7 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - CIRCFUM REBAR
8.1 ft. - Surface Reinforcement Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR
15.9 ft. - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: YES - CIRCUM
34.7 ft. - General Observation - MAG COAT 40% START
60.4 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM BAR
124.5 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR
285.4 ft. - Surface Reinforcement Visible, from 11 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR
335.8 ft. - General Observation - 40% MAG COAT
| Distance | Code | Observation |
|---|---|---|
| 369 | SAM | SEVERE AGG |
| 285.4 | SRV | CIRCUM REBAR |
| 67.2 | SRV | CIRCUM REBAR |
| 335.8 | MGO | 40% MAG COAT |
| 0 | MGO | MH CONN 9:00 ACTIVE INCONING LINE |
| 369.8 | AMH | 2:45AM |
| 60.4 | SRV | CIRCUM BAR |
| 124.5 | SRV | CIRCUM REBAR |
| 15.9 | SRC | CIRCUM |
| 0 | MGO | MH CONN 6:00 ACTIVE INCOMING LINE |
| 7 | SRC | CIRCFUM REBAR |
| 0 | AMH | 2:05AM |
| 34.7 | MGO | MAG COAT 40% START |
| 7.9 | SAP | — |
| 0 | MGO | MH CONN 3:00 ACTIVE OUTGOING LINE |
| 369 | MGO | MAG COAT 40% FINISH |
| 2 | SRV | CIRCUM REBAR |
| 8.1 | SRP | CIRCUM REBAR |
| 34.7 | SRC | CIRCUM REBAR |
| 2 | MGO | MAG COAT 10% START 8:00 TO 4:00 |
| 0 | MWM | — |
| 2 | SAM | SEVERE AGG |
| 369 | MGO | MH CONN 3:00 ACTIVE |
| 7 | SRV | CIRCUM REBAR |
| 0 | MWL | — |