Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 14, 2017, 04:27 PM
  • 29 0206_29 0205_8142017_092951.mp4

Date
08/14/2017
W/O
PENDING
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z01026
PipeID
P24108
Time
9:27 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7490
Sewer Name
29 28TH STREET PUMPING PLANT SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
20170814DF_28TH_ST_P_P_SEWER
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
29 0206
Downstream MH
29 0205
Dir. of Survey
Downstream
Length Surveyed
251.9 ft.
Total Length
251.9 ft.
Structural Index
3
Structural Quick
5232
Structural Rating
22
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
24
Pipe schematic from manhole 29 0206 to 29 0205
MH: 29 0206MH: 29 0205downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 9:28 AM0 ft. MGO - General Observation - ROACHES @ MH2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start39.5 ft. TBC - Tap Break-In Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"62.1 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 4"90.2 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"112.7 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 4"128.8 ft. MGP - General Photograph - CHIPPING @ 9 O'CLOCK139.8 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4" - Open146.3 ft. MGP - General Photograph - BROKEN PIPE146.3 ft. B - Broken, from 06 to 10 o'clock, within 8 inches of joint: YES162.1 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES162.1 ft. B - Broken, from 06 to 10 o'clock, within 8 inches of joint: YES163.1 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 4"174.5 ft. MGP - General Photograph - SPALLING190.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"202 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES212.7 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 4"224.5 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES225 ft. CM - Crack Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES240.4 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"250.1 ft. MGO - General Observation - Grease Throughout The Reach (5%)250.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish250.1 ft. MGO - General Observation - ROACHES @ MH251.9 ft. AMH - Downstream Manhole, Survey Ends - 10:00 AM

Observation photos (10)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph - CHIPPING @ 9 O'CLOCK

    128.8 ft. - General Photograph - CHIPPING @ 9 O'CLOCK

  • General Photograph - BROKEN PIPE

    146.3 ft. - General Photograph - BROKEN PIPE

  • Broken, from 06 to 10 o'clock, within 8 inches of joint: YES

    146.3 ft. - Broken, from 06 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    162.1 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Broken, from 06 to 10 o'clock, within 8 inches of joint: YES

    162.1 ft. - Broken, from 06 to 10 o'clock, within 8 inches of joint: YES

  • General Photograph - SPALLING

    174.5 ft. - General Photograph - SPALLING

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    202 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    224.5 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES

    225 ft. - Crack Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES

Observations (28)

DistanceCodeObservation
250.1MGOGrease Throughout The Reach (5%)
190.3TFC
224.5CL
0MGOConn. @ Mh, 3 O' Clock. Active
0MWL
112.7TFC
250.1SSS
2SSS
212.7TFC
225CM
0MWM
62.1TFC
174.5MGPSPALLING
146.3MGPBROKEN PIPE
128.8MGPCHIPPING @ 9 O'CLOCK
146.3B
163.1TFC
202CL
139.8TFOpen
39.5TBC
90.2TFC
162.1FL
162.1B
240.4TFC
0AMH9:28 AM
0MGOROACHES @ MH
250.1MGOROACHES @ MH
251.9AMH10:00 AM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2017-08-14T09:27:45-07:00
documentation
FRANKLIN, IGNACIO
is_lateral_inspection
false