Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 16, 2017, 09:56 AM
  • Section#12_F 0202_F 0201__8162017__G6802.mp4

Date
08/16/2017
W/O
0646419
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00048
PipeID
P10332
Time
2:56 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6803
Sewer Name
F JOINT OUTFALL F - UNIT 7F
City
CERRITOS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
38
Purpose
Capital Improvement Program Assesment
Project
20170812MDM_JOINT_OUTFALL_F_UNIT_7F
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Upstream MH
F 0202
Downstream MH
F 0201
Dir. of Survey
Downstream
Length Surveyed
160.6 ft.
Total Length
160.6 ft.
Structural Index
2
Structural Quick
2F00
Structural Rating
66
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
68
Pipe schematic from manhole F 0202 to F 0201
MH: F 0202MH: F 0201downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - MH CONN 9:00 ACTIVE0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 5:30AM2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT2 ft. MGO - General Observation - MAG COAT 80% START 8:00 TO 4:002.2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 07 to 09 o'clock, , within 8 inches of joint: NO36.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING PEELING CONCRETE117.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB160.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE160.1 ft. MGO - General Observation - MAG COAT 80% FINISH160.6 ft. AMH - Downstream Manhole, Survey Ends - 5:45AM

Observation photos (4)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • General Observation - MAG COAT 80% START 8:00 TO 4:00

    2 ft. - General Observation - MAG COAT 80% START 8:00 TO 4:00

  • Deposits Attached Grease, 10 %of cross sectional area, from 07 to 09 o'clock,  , within 8 inches of joint: NO

    2.2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 07 to 09 o'clock, , within 8 inches of joint: NO

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING PEELING CONCRETE

    36.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING PEELING CONCRETE

Observations (12)

DistanceCodeObservation
117.7TFCSTUB
0MWM
0MGOMH CONN 9:00 ACTIVE
2.2DAGS
36.6SSSBLISTERING PEELING CONCRETE
2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
160.1SSSBLISTERING PEELING CONCRETE
0MWL
0AMH5:30AM
160.1MGOMAG COAT 80% FINISH
160.6AMH5:45AM
2MGOMAG COAT 80% START 8:00 TO 4:00

Properties (6)

custom_field_three
80% MAG COAT
custom_field_two
5
customer
LACSD
datetime
2017-08-16T02:56:26-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false