Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 15, 2017, 10:11 AM
  • Section#5_F 0209_F 0208__8152017__G6801.mp4

Date
08/15/2017
W/O
0646419
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00048
PipeID
P10339
Time
3:11 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6801
Sewer Name
F JOINT OUTFALL F - UNIT 7F
City
CERRITOS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
38
Purpose
Capital Improvement Program Assesment
Project
20170812MDM_JOINT_OUTFALL_F_UNIT_7F
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Upstream MH
F 0209
Downstream MH
F 0208
Dir. of Survey
Downstream
Length Surveyed
506.5 ft.
Total Length
506.5 ft.
Structural Index
2
Structural Quick
2S00
Structural Rating
202
O&M Index
3
O&M Quick
3623
O&M Rating
24
Overall Index
2
Overall Quick
Overall Rating
226
Pipe schematic from manhole F 0209 to F 0208
MH: F 0209MH: F 0208downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:30AM0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT2 ft. MGO - General Observation - OLD MAG COAT 98% START 8:00 TO 4:0029 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 02 to 04 o'clock, , within 8 inches of joint: YES29 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB41.9 ft. MGO - General Observation - 98% OLD MAG COAT ON PIPE44.7 ft. MGP - General Photograph - OLD MAG COAT125.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB125.1 ft. DAE - Deposits Attached Encrustation, 15 %of cross sectional area, from 01 to 05 o'clock, , within 8 inches of joint: YES208.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB208.8 ft. DAE - Deposits Attached Encrustation, 20 %of cross sectional area, from 01 to 05 o'clock, , within 8 inches of joint: YES316.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB316.5 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 01 to 05 o'clock, , within 8 inches of joint: YES364.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE364.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 11 o'clock, , within 8 inches of joint: YES366.6 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES399.9 ft. DAE - Deposits Attached Encrustation, 15 %of cross sectional area, from 01 to 05 o'clock, , within 8 inches of joint: YES399.9 ft. DAE - Deposits Attached Encrustation, 15 %of cross sectional area, from 01 to 05 o'clock, , within 8 inches of joint: YES428.7 ft. MGO - General Observation - 98% OLD MAG COAT493.3 ft. MGP - General Photograph493.3 ft. DAE - Deposits Attached Encrustation, 15 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES506.1 ft. MGO - General Observation - OLD MAG COAT 98% FINISH506.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE UNDER MAG COAT506.5 ft. AMH - Downstream Manhole, Survey Ends - 4:25AM

Observation photos (17)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • General Observation - OLD MAG COAT 98% START 8:00 TO 4:00

    2 ft. - General Observation - OLD MAG COAT 98% START 8:00 TO 4:00

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 02 to 04 o'clock,  , within 8 inches of joint: YES

    29 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 02 to 04 o'clock, , within 8 inches of joint: YES

  • General Observation - 98% OLD MAG COAT ON PIPE

    41.9 ft. - General Observation - 98% OLD MAG COAT ON PIPE

  • General Photograph - OLD MAG COAT

    44.7 ft. - General Photograph - OLD MAG COAT

  • Deposits Attached Encrustation, 15 %of cross sectional area, from 01 to 05 o'clock,  , within 8 inches of joint: YES

    125.1 ft. - Deposits Attached Encrustation, 15 %of cross sectional area, from 01 to 05 o'clock, , within 8 inches of joint: YES

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB

    208.8 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB

  • Deposits Attached Encrustation, 20 %of cross sectional area, from 01 to 05 o'clock,  , within 8 inches of joint: YES

    208.8 ft. - Deposits Attached Encrustation, 20 %of cross sectional area, from 01 to 05 o'clock, , within 8 inches of joint: YES

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB

    316.5 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 01 to 05 o'clock,  , within 8 inches of joint: YES

    316.5 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 01 to 05 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 11 o'clock,  , within 8 inches of joint: YES

    364.2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 11 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Grease, 15 %of cross sectional area, from 04 to 05 o'clock,  , within 8 inches of joint: YES

    366.6 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 15 %of cross sectional area, from 01 to 05 o'clock,  , within 8 inches of joint: YES

    399.9 ft. - Deposits Attached Encrustation, 15 %of cross sectional area, from 01 to 05 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 15 %of cross sectional area, from 01 to 05 o'clock,  , within 8 inches of joint: YES

    399.9 ft. - Deposits Attached Encrustation, 15 %of cross sectional area, from 01 to 05 o'clock, , within 8 inches of joint: YES

  • General Observation - 98% OLD MAG COAT

    428.7 ft. - General Observation - 98% OLD MAG COAT

  • General Photograph

    493.3 ft. - General Photograph

  • Deposits Attached Encrustation, 15 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    493.3 ft. - Deposits Attached Encrustation, 15 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

Observations (26)

DistanceCodeObservation
0MWL
399.9DAE
506.5AMH4:25AM
208.8TFCSTUB
125.1TFCSTUB
2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
364.2TFACTIVE
366.6DAGS
0AMH3:30AM
29DAE
316.5TFCSTUB
29TFCSTUB
399.9DAE
428.7MGO98% OLD MAG COAT
0MWM
2MGOOLD MAG COAT 98% START 8:00 TO 4:00
208.8DAE
125.1DAE
41.9MGO98% OLD MAG COAT ON PIPE
493.3MGP
506.1MGOOLD MAG COAT 98% FINISH
506.1SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
44.7MGPOLD MAG COAT
316.5DAE
493.3DAE
364.2DAE

Properties (6)

custom_field_three
98% OLD MAG COAT
custom_field_two
5
customer
LACSD
datetime
2017-08-15T03:11:13-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false