Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 10, 2017, 05:12 PM
  • H 0188_H 0187_8102017_104128.mp4

Date
08/10/2017
W/O
0635578
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00168
PipeID
P10635
Time
10:12 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7488
Sewer Name
H JOINT OUTFALL H - UNIT 2B
City
BELL GARDENS
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
20170810SHO_JOINT_OUTFALL_H_UNIT_2B
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Upstream MH
H 0188
Downstream MH
H 0187
Dir. of Survey
Downstream
Length Surveyed
462.6 ft.
Total Length
462.6 ft.
Structural Index
4
Structural Quick
5431
Structural Rating
25
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
29
Pipe schematic from manhole H 0188 to H 0187
MH: H 0188MH: H 0187downstream0 ft. MGO - General Observation - ACTIVE CONN. @ THE MH, 9 O CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 10350 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO, Start8 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - FIRST 6 FEET11.1 ft. SRV - Surface Reinforcement Visible, from 09 to 01 o'clock, within 8 inches of joint: NO17.3 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO, Finish21.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start34.8 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO458.8 ft. MGO - General Observation - FLOW BAND ATTACHED AROUND THE PIPE461.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish461.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish462.6 ft. AMH - Downstream Manhole, Survey Ends - 1115

Observation photos (7)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO, Start

    8 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - FIRST 6 FEET

    8 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - FIRST 6 FEET

  • Surface Reinforcement Visible, from 09 to 01 o'clock, within 8 inches of joint: NO

    11.1 ft. - Surface Reinforcement Visible, from 09 to 01 o'clock, within 8 inches of joint: NO

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    21.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO

    34.8 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO

  • General Observation - FLOW BAND ATTACHED AROUND THE PIPE

    458.8 ft. - General Observation - FLOW BAND ATTACHED AROUND THE PIPE

Observations (15)

DistanceCodeObservation
11.1SRV
21.6SSS
8SAV
461.8SSS
461.8SAV
17.3SRV
8SRV
0MGOACTIVE CONN. @ THE MH, 9 O CLOCK
34.8SRV
462.6AMH1115
8SRVFIRST 6 FEET
0AMH1035
0MWL
0MWM
458.8MGOFLOW BAND ATTACHED AROUND THE PIPE

Properties (6)

custom_field_three
VISIBLE/PROJECTING AGG. & REBAR
custom_field_two
2
customer
LACSD
datetime
2017-08-10T10:12:31-07:00
documentation
OBREGON, IGNACIO, FRANKLIN, BRAR
is_lateral_inspection