Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 15, 2016, 06:22 AM
  • 02 1165_02 1164_14112016_222521.mp4

Date
11/14/2016
W/O
602603
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00351
PipeID
P02949
Time
10:22 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3824
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
WO_602603_TV02060_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
02 1165
Downstream MH
02 1164
Dir. of Survey
Downstream
Length Surveyed
227.7 ft.
Total Length
227.7 ft.
Structural Index
3
Structural Quick
3F22
Structural Rating
115
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
116
Pipe schematic from manhole 02 1165 to 02 1164
MH: 02 1165MH: 02 1164downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 11650 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area5.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"7.2 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES7.5 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"8.4 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES27.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES39.9 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: NO, 6ft45.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start57.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"106.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"156.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"208.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"227.4 ft. MGO - General Observation - CAPPED LATERAL 3 O'CLOCK @ MH227.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish227.7 ft. AMH - Downstream Manhole, Survey Ends - 02 1164

Observation photos (6)

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    7.2 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    7.5 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES

    8.4 ft. - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    27.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: NO, 6ft

    39.9 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: NO, 6ft

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    45.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
39.9CL
0AMH02 1165
227.4MGOCAPPED LATERAL 3 O'CLOCK @ MH
5.1TFC
208.7TF
45.5CM
227.6CM
0MWM
27.6CM
106.1TFC
156.9TF
8.4RFJ
227.7AMH02 1164
7.5TB
0MWL
7.2CL
57.3TF

Properties (6)

additional_info
SC304573
custom_field_two
3
customer
LACSD
datetime
2016-11-14T22:22:55-08:00
documentation
PROPIPE
is_lateral_inspection
false