Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 16, 2016, 06:53 AM
  • 02 1163_02 1162_15112016_225321.mp4

Date
11/15/2016
W/O
602603
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00351
PipeID
P02947
Time
10:53 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3825
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
WO_602603_TV02060_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
02 1163
Downstream MH
02 1162
Dir. of Survey
Downstream
Length Surveyed
234 ft.
Total Length
234 ft.
Structural Index
3
Structural Quick
3E23
Structural Rating
97
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
97
Pipe schematic from manhole 02 1163 to 02 1162
MH: 02 1163MH: 02 1162downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 11630 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area10.2 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES25.7 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES48 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"49.4 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES53.2 ft. CC - Crack Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES54 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"64.9 ft. CS - Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES83.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start102.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"154.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"205.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"227.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish234 ft. AMH - Downstream Manhole, Survey Ends - 02 1162

Observation photos (7)

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    10.2 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    25.7 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    48 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    49.4 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES

    53.2 ft. - Crack Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES

    64.9 ft. - Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    83.7 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
83.7CM
0AMH02 1163
0MWL
25.7CL
54TF
48TB
64.9CS
205.6TFC
0MWM
53.2CC
154.6TFC
102.8TFC
227.5CM
49.4CM
10.2CL
234AMH02 1162

Properties (6)

additional_info
SC304574
custom_field_two
3
customer
LACSD
datetime
2016-11-15T22:53:03-08:00
documentation
PROPIPE
is_lateral_inspection
false