Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 1, 2016, 12:15 PM
  • 02 1452_02 2129_12012016_041824.mp4

Date
12/01/2016
W/O
602592
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00307
PipeID
P04693
Time
4:15 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3928
Sewer Name
02 TRACT #5445 TRUNK
City
LOS ANGELES, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
13
Purpose
Routine Assessment
Project
WO_602592_TV02117_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1452
Downstream MH
02 2129
Dir. of Survey
Downstream
Length Surveyed
33.7 ft.
Total Length
33.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 02 1452 to 02 2129
MH: 02 1452MH: 02 2129downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 14520 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start31.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish33.7 ft. AMH - Downstream Manhole, Survey Ends - 02 212933.7 ft. MGO - General Observation - LATERAL AT MH 9 O CLOCK

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
31.5DAGS
33.7AMH02 2129
0AMH02 1452
33.7MGOLATERAL AT MH 9 O CLOCK
4DAGS
0MWL
0MWM

Properties (6)

additional_info
SC317672
custom_field_two
4
customer
LACSD
datetime
2016-12-01T04:15:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false