Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 1, 2016, 07:21 AM
  • 02 1442_02 1441_11302016_233245.mp4

Date
11/30/2016
W/O
602592
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00307
PipeID
P04682
Time
11:21 PM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3928
Sewer Name
02 TRACT #5445 TRUNK
City
LOS ANGELES, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
13
Purpose
Routine Assessment
Project
WO_602592_TV02117_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 1442
Downstream MH
02 1441
Dir. of Survey
Downstream
Length Surveyed
341.4 ft.
Total Length
341.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 02 1442 to 02 1441
MH: 02 1442MH: 02 1441downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 14423.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start334.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish337 ft. MGO - General Observation - LATERAL AT MH 9 O CLOCK341.4 ft. AMH - Downstream Manhole, Survey Ends - 02 1441

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
341.4AMH02 1441
0MWM
0MWL
334.9DAGS
3.4DAGS
337MGOLATERAL AT MH 9 O CLOCK
0AMH02 1442

Properties (6)

additional_info
SC317672
custom_field_two
4
customer
LACSD
datetime
2016-11-30T23:21:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false