Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 29, 2016, 06:30 AM
  • 02 1459_02 1458_11282016_225358.mp4

Date
11/28/2016
W/O
602592
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00307
PipeID
P04702
Time
10:30 PM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3926
Sewer Name
02 TRACT #5445 TRUNK
City
LOS ANGELES, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
13
Purpose
Routine Assessment
Project
WO_602592_TV02117_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
02 1459
Downstream MH
02 1458
Dir. of Survey
Downstream
Length Surveyed
294.3 ft.
Total Length
294.3 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 02 1459 to 02 1458
MH: 02 1459MH: 02 1458downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 14590 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 3 O CLOCK7.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start60.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES62.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"65.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"75.6 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES114.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"116.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"162.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"164.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"210.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"219.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"258.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"263.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"290.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"292.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish294.3 ft. AMH - Downstream Manhole, Survey Ends - 02 1458

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    7.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    60.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    75.6 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
0AMH02 1459
0MWM
116.8TFC
0MWL
294.3AMH02 1458
75.6CL
114.7TFA
62.8TFA
60.8CL
210.1TFA
290.7TF
65.4TFC
0MGOLATERAL AT MH 3 O CLOCK
219.4TFA
258.8TFA
162.4TF
164.4TFA
263.4TFA
292.2DAGS
7.1DAGS

Properties (6)

additional_info
SC317669
custom_field_two
4
customer
LACSD
datetime
2016-11-28T22:30:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false