Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 4, 2016, 09:12 AM
  • 02 1126_02 1125_11042016_021451.mp4

Date
11/04/2016
W/O
602268
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00351
PipeID
P02906
Time
2:12 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3907
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
14
Purpose
Routine Assessment
Project
WO_602268_TV02061_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1126
Downstream MH
02 1125
Dir. of Survey
Downstream
Length Surveyed
268.2 ft.
Total Length
268.2 ft.
Structural Index
3
Structural Quick
3F21
Structural Rating
113
O&M Index
2
O&M Quick
412T
O&M Rating
216
Overall Index
2
Overall Quick
Overall Rating
329
Pipe schematic from manhole 02 1126 to 02 1125
MH: 02 1126MH: 02 1125downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 11260 ft. MWL - Water Level, 25 %of cross sectional area2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start34 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES43.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"77.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES85.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start95 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"146.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"197.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"244.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"266 ft. MGO - General Observation - COCKROACHES IN MANHOLE266 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish266 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish266 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish268.2 ft. AMH - Downstream Manhole, Survey Ends - 02 1125

Observation photos (7)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    34 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    77.2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    85.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    266 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (19)

DistanceCodeObservation
266MGOCOCKROACHES IN MANHOLE
2DAE
0MGOCOCKROACHES IN MANHOLE
34CL
43.5TFC
266DAGS
0MWM
266CM
197.3TFC
95TFC
268.2AMH02 1125
0AMH02 1126
85.4CM
77.2CM
0MWL
244.7TFC
2DAGS
266DAE
146.1TFC

Properties (6)

additional_info
SC306345
custom_field_two
3
customer
LACSD
datetime
2016-11-04T02:12:35-07:00
documentation
PRO PIPE
is_lateral_inspection
false