Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 7, 2016, 12:08 PM
  • 02 1135_02 1134_07112016_040902.mp4

Date
11/07/2016
W/O
602268
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00351
PipeID
P02917
Time
4:08 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3817
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
13
Purpose
Routine Assessment
Project
WO_602268_TV02061_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1135
Downstream MH
02 1134
Dir. of Survey
Downstream
Length Surveyed
339 ft.
Total Length
339.1 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
198
O&M Index
3
O&M Quick
4211
O&M Rating
9
Overall Index
3
Overall Quick
Overall Rating
207
Pipe schematic from manhole 02 1135 to 02 1134
MH: 02 1135MH: 02 1134downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 6 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 02 11350 ft. MWL - Water Level, 10 %of cross sectional area10 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES14.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start65.4 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"69.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"72.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"119.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"122.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"166.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"169 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"192.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"220.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"222.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"270.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"273.2 ft. RFL - Roots Fine Lateral, at 02 o'clock273.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"320.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"323.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"339.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish339.1 ft. AMH - Downstream Manhole, Survey Ends - 02 1134

Observation photos (5)

  • Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    10 ft. - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    14.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    65.4 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    192.3 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Roots Fine Lateral, at 02 o'clock

    273.2 ft. - Roots Fine Lateral, at 02 o'clock

Observations (23)

DistanceCodeObservation
0MWM
14.1CM
323.8TF
339.1CM
65.4TB
192.3TB
122.6TFC
169TF
0MGOCONNECTION AT MH 6 O'CLOCK
339.1AMH02 1134
10CM
119.7TF
273.2RFL
273.2TF
222.8TFC
0AMH02 1135
0MWL
320.8TF
220.4TFC
166.2TFC
72.1TF
69.5TFC
270.3TFC

Properties (6)

additional_info
SC304566
custom_field_two
3
customer
LACSD
datetime
2016-11-07T04:08:35-08:00
documentation
PRO-PIPE
is_lateral_inspection
false