Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 8, 2016, 09:00 AM
  • 02 1120_02 1119 _08112016_010041.mp4

Date
11/08/2016
W/O
602268
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00351
PipeID
P02899
Time
1:00 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3818
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
14
Purpose
Routine Assessment
Project
WO_602268_TV02061_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1120
Downstream MH
02 1119
Dir. of Survey
Downstream
Length Surveyed
292 ft.
Total Length
292.1 ft.
Structural Index
3
Structural Quick
3I21
Structural Rating
158
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
160
Pipe schematic from manhole 02 1120 to 02 1119
MH: 02 1120MH: 02 1119downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 11200 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area9.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"13.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"22.1 ft. CS - Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES30.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start60.1 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - BROKEN63.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"110.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"113.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"161.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"164.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"168.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"215.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"218 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"262.6 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"265.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"268.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"292.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish292.1 ft. AMH - Downstream Manhole, Survey Ends - 02 1119

Observation photos (4)

  • Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

    22.1 ft. - Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    30.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - BROKEN

    60.1 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - BROKEN

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    161.8 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (21)

DistanceCodeObservation
218TFC
262.6TB
0AMH02 1120
215.2TFC
292.1CM
9.5TF
0MWM
13.9TFC
60.1TFDBROKEN
161.8TB
168.3TF
113.8TF
164.7TFC
63.7TF
268.7TFC
0MWL
265.4TF
292.1AMH02 1119
110.7TFC
22.1CS
30.5CM

Properties (6)

additional_info
SC304567
custom_field_two
3
customer
LACSD
datetime
2016-11-08T01:00:08-08:00
documentation
PRO-PIPE
is_lateral_inspection
false