Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 8, 2016, 09:30 AM
  • 01 0522_01 0521_08112016_013100.mp4

Date
11/08/2016
W/O
602233
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00206
PipeID
P01007
Time
1:30 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3874
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_602233_TV01017_NOV2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0521
Downstream MH
01 0522
Dir. of Survey
Upstream
Length Surveyed
384.6 ft.
Total Length
384.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 01 0521 to 01 0522
MH: 01 0521MH: 01 0522upstream0 ft. MGO - General Observation - ROACHES IN MH0 ft. MGO - General Observation - PIECE OF CLAY PIPE0 ft. AMH - Upstream Manhole, Survey Ends - 01 05220 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK ACTIVE AT MH3.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish68.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"71.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"80 ft. OBN - Obstacles Construction Debris, 15 %of cross sectional area, from 04 to 08 o'clock, Finish140.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"145.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"220 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"247.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"250.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"295.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"321.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"336 ft. OBN - Obstacles Construction Debris, 15 %of cross sectional area, from 04 to 08 o'clock, Start - NOT VISIBLE366.7 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"382.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start384.6 ft. MWL - Water Level, 10 %of cross sectional area384.6 ft. MGO - General Observation - ROACHES IN MH384.6 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK CAPPED384.6 ft. AMH - Downstream Manhole, Survey Begins - 01 0521384.6 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK ACTIVE384.6 ft. MWM - Water Mark, 15 %of cross sectional area

Observation photos (12)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"

    17.9 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    63.2 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    89.2 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    134.3 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    137.3 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"

    164.6 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    238.8 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    244.3 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"

    313.3 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    315.9 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Finish

    381.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observations (24)

DistanceCodeObservation
315.9TFC
137.3TFC
384.6MGOROACHES IN MH
238.8TF
0MWL
63.2TF
134.3TFC
0MGOROACHES IN MH
164.6TBA
0MGOLATERAL AT MH 9 OCLOCK CAPPED
2.1DAGS
313.3TFC
381.3DAGS
244.3TF
384.6MGOPIECE OF CLAY PIPE
384.6AMH01 0522
89.2TFC
0AMH01 0521
17.9TBA
384.6MGOLATERAL AT MH 9 OCLOCK ACTIVE AT MH
304.6OBN
0MGOLATERAL AT MH 3 OCLOCK ACTIVE
48.6OBNNOT VISIBLE
0MWM

Properties (6)

additional_info
SC305204
custom_field_two
4
customer
LACSD
datetime
2016-11-08T01:30:40-08:00
documentation
PRO PIPE
is_lateral_inspection
false