Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 5, 2017, 08:21 PM
  • 29 0522_29 0521_652017_132303.mp4

Date
06/05/2017
W/O
0641042
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z01106
PipeID
P24574
Time
1:21 PM
Certificate
415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7426
Sewer Name
29 19TH STREET SEWER
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Capital Improvement Program Assesment
Project
20170605DF_19TH_ST_SEWER
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
29 0522
Downstream MH
29 0521
Dir. of Survey
Downstream
Length Surveyed
266 ft.
Total Length
266 ft.
Structural Index
2
Structural Quick
3924
Structural Rating
39
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
41
Pipe schematic from manhole 29 0522 to 29 0521
MH: 29 0522MH: 29 0521downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:21 PM0 ft. MGO - General Observation - ROACHES @ MH2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11.3 ft. CM - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES17.4 ft. CM - Crack Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES22.7 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES30.6 ft. CS - Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES61.7 ft. CS - Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES72.1 ft. CS - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES78.7 ft. JOM - Joint Offset Medium, 1"79.5 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: YES, 4"81.2 ft. JOM - Joint Offset Medium, 1"96.5 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Open162.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES179.8 ft. JOM - Joint Offset Medium, 1"180.7 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: YES, 4"181.4 ft. JOM - Joint Offset Medium, 1"191.4 ft. CM - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES - CHIPPING ALSO197.5 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 4" - Open199.1 ft. FS - Fracture Spiral, from 04 to 05 o'clock, within 8 inches of joint: YES220 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES238.3 ft. MGP - General Photograph - CHIPPING240.7 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES246 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES253.2 ft. MGP - General Photograph - SPALLING264.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish264.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish265 ft. MGO - General Observation - ROACHES @ MH266 ft. AMH - Downstream Manhole, Survey Ends - 1:58 PM

Observation photos (19)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    11.3 ft. - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES

    17.4 ft. - Crack Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    22.7 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES

    30.6 ft. - Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES

    61.7 ft. - Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

    72.1 ft. - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Joint Offset Medium, 1"

    78.7 ft. - Joint Offset Medium, 1"

  • Joint Offset Medium, 1"

    81.2 ft. - Joint Offset Medium, 1"

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    162.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Joint Offset Medium, 1"

    179.8 ft. - Joint Offset Medium, 1"

  • Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES - CHIPPING ALSO

    191.4 ft. - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES - CHIPPING ALSO

  • Fracture Spiral, from 04 to 05 o'clock, within 8 inches of joint: YES

    199.1 ft. - Fracture Spiral, from 04 to 05 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES

    220 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES

  • General Photograph - CHIPPING

    238.3 ft. - General Photograph - CHIPPING

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    240.7 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    246 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • General Photograph - SPALLING

    253.2 ft. - General Photograph - SPALLING

Observations (32)

DistanceCodeObservation
240.7FL
265MGOROACHES @ MH
253.2MGPSPALLING
72.1CS
79.5TFA
191.4CMCHIPPING ALSO
81.2JOM
266AMH1:58 PM
0MWM
78.7JOM
264.8SSS
0MWL
22.7FL
238.3MGPCHIPPING
11.3CM
246CM
199.1FS
220DAGS
180.7TFA
30.6CS
61.7CS
0AMH1:21 PM
179.8JOM
162.9CM
181.4JOM
2SSS
264.9CM
2CM
197.5TFOpen
96.5TFOpen
0MGOROACHES @ MH
17.4CM

Properties (6)

additional_info
TAPE NUMBER (G7425) IS WRONG ON SCREEN. CORRECT TAPE IS NUMBER (G7426)
custom_field_two
3
customer
LACSD
datetime
2017-06-05T13:21:36-07:00
documentation
FRANKLIN, IGNACIO, BRAR
is_lateral_inspection
false