A 0509_A 0508_462017_033140.mp4
2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG
2 ft. - General Observation - MAG COAT 90% START 9:00 TO 3:00
9.6 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR
13.1 ft. - Surface Reinforcement Visible, from 12 to 03 o'clock, within 8 inches of joint: YES, Start
35.5 ft. - Surface Reinforcement Visible, from 12 to 03 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR UNDER MAG COAT
44.6 ft. - Surface Reinforcement Visible, from 12 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR
66.3 ft. - Surface Reinforcement Visible, from 12 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR
76.1 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR CORRODED & MISSING
86.4 ft. - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: YES - CORRODE MISSING REBAR
125 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CORRODED MISSING REBAR
156.5 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR
181.7 ft. - Surface Reinforcement Corroded, from 11 to 02 o'clock, within 8 inches of joint: NO, Start - CORRODEDBEYOUND REBAR
184.1 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CORRODED BEYOUND REBAR
187.9 ft. - Surface Reinforcement Corroded, from 11 to 02 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR
197.7 ft. - Surface Reinforcement Corroded, from 12 to 01 o'clock, within 8 inches of joint: NO - ALL REBAR MISSING
201 ft. - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - CORRODED BRYOUND REBAR
204.4 ft. - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR
210 ft. - Surface Reinforcement Corroded, from 12 to 01 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR
210 ft. - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR
220.2 ft. - Surface Reinforcement Corroded, from 11 to 02 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR
| Distance | Code | Observation |
|---|---|---|
| 44.6 | SRV | CIRCUM REBAR |
| 0 | MWL | — |
| 204.4 | SRC | CORRODED BEYOUND REBAR |
| 76.1 | SRC | CIRCUM REBAR CORRODED & MISSING |
| 9.6 | SRV | CIRCUM REBAR |
| 197.7 | SRC | ALL REBAR MISSING |
| 76.1 | MGO | MAG COAY 90% FINISH |
| 204.4 | MGO | NEW DVD#H0485 |
| 86.4 | SRC | CORRODE MISSING REBAR |
| 223.2 | SRV | LONG REBAR |
| 220.2 | SRC | CORRODED BEYOUND REBAR |
| 35.5 | SRV | CIRCUM REBAR UNDER MAG COAT |
| 223.2 | SAM | SEVERE AGG |
| 187.9 | SRC | CORRODED BEYOUND REBAR |
| 156.5 | SRV | LONG REBAR |
| 2 | SAM | SEVERE AGG |
| 223.2 | MGO | Conn. @ Mh, 3 O' Clock. Active OUTGOING LINE |
| 184.1 | SRC | CORRODED BEYOUND REBAR |
| 0 | MWM | — |
| 125 | SRC | CORRODED MISSING REBAR |
| 181.7 | SRC | CORRODEDBEYOUND REBAR |
| 201 | SRC | CORRODED BRYOUND REBAR |
| 223.2 | SRC | CORRODED BEYOUND REBAR |
| 2 | MGO | MAG COAT 90% START 9:00 TO 3:00 |
| 223.2 | SRC | CORRODED BEYOUND REBAR |
| 223.6 | AMH | 5:00AM |
| 223.2 | SRC | CORRODED CIRCUM REBAR |
| 210 | SRC | CORRODED BEYOUND REBAR |
| 0 | AMH | 3:30AM |
| 13.1 | SRV | — |
| 66.3 | SRV | CIRCUM REBAR |
| 76.1 | SRV | CIRCUM REBAR UNDER MAG COAT |
| 210 | SRC | CORRODED BEYOUND REBAR |
| 24.7 | SRV | CIRCUM REBAR |