Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 30, 2017, 07:20 PM
  • 21 0940_21 0939_3302017_123047.mp4

Date
03/30/2017
W/O
0618972
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00760
PipeID
P16033
Time
12:20 PM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7372
Sewer Name
21 CLAREMONT OUTFALL TRUNK
City
CLAREMONT
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20170330DF_CLAREMONT_OUTFALL_TRUNK
Material
NRCP
Shape
Circular
Height
12 in.
Upstream MH
21 0940
Downstream MH
21 0939
Dir. of Survey
Downstream
Length Surveyed
201.8 ft.
Total Length
201.8 ft.
Structural Index
3
Structural Quick
453A
Structural Rating
55
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
55
Pipe schematic from manhole 21 0940 to 21 0939
MH: 21 0940MH: 21 0939downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:22 PM2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 75% MAG COAT2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start13.5 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES23.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES31.1 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES46.4 ft. CM - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES53.7 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES56.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES61.1 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES67.6 ft. FM - Fracture Multiple, from 04 to 06 o'clock, within 8 inches of joint: YES71.4 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES81 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES83.8 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES86.1 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES95.9 ft. FL - Fracture Longitudinal, at 05 o'clock, within 8 inches of joint: YES98.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start200 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish200 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish200 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish200.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish200.8 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 75% MAG COAT201.8 ft. AMH - Downstream Manhole, Survey Ends - 1:02 PM

Observation photos (16)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    13.5 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    23.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    31.1 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

    46.4 ft. - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    53.7 ft. - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    56.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    61.1 ft. - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 04 to 06 o'clock, within 8 inches of joint: YES

    67.6 ft. - Fracture Multiple, from 04 to 06 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    71.4 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    81 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    83.8 ft. - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    86.1 ft. - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 05 o'clock, within 8 inches of joint: YES

    95.9 ft. - Fracture Longitudinal, at 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    98.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (28)

DistanceCodeObservation
61.1FL
0MGOConn. @ Mh, 3 O' Clock. Active
2SZ75% MAG COAT
200SSS
0MWM
2SSS
67.6FM
2SAV
0MWL
53.7FL
95.9FL
71.4FM
2CM
200CM
13.5FL
46.4CM
23.9FM
81FM
86.1FL
31.1FL
56.4CM
98.5FM
200.8SZ75% MAG COAT
0AMH12:22 PM
200.1FM
83.8FL
201.8AMH1:02 PM
200SAV

Properties (6)

custom_field_three
SEVERE FRACTURES/POSSIBLY BROKEN
custom_field_two
2
customer
LACSD
datetime
2017-03-30T12:20:03-07:00
documentation
FRANKLIN, MIRANDA, IGNACIO, BRAR, SHADLER
is_lateral_inspection
false