Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 22, 2017, 09:22 AM
  • 02 0603_02 0602A _22052017_022258.mp4

Date
05/22/2017
W/O
618894
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00258
PipeID
P03149
Time
2:22 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4558
Sewer Name
02 EAST COMPTON BOULEVARD EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
33
Purpose
Routine Assessment
Project
WO_618894_TV02057_MAY2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0603
Downstream MH
02 0602A
Dir. of Survey
Downstream
Length Surveyed
207.1 ft.
Total Length
207.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2G00
O&M Rating
82
Overall Index
2
Overall Quick
Overall Rating
85
Pipe schematic from manhole 02 0603 to 02 0602A
MH: 02 0603MH: 02 0602Adownstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 06030 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start75.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"118.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES179.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"204.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish207 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK207.1 ft. AMH - Downstream Manhole, Survey Ends - 02 0602A207.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    118.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
0MWL
118.1CM
75.8TFC
207.1AMH02 0602A
0AMH02 0603
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
207MGOACTIVE CONNECTION AT MH 3 O'CLOCK
204.6DAGS
207.1MGOCOCKROACHES IN MANHOLE
2DAGS
179.1TFC
0MGOCOCKROACHES IN MANHOLE
0MWM

Properties (6)

additional_info
SC345234
custom_field_two
4
customer
LACSD
datetime
2017-05-22T02:22:23-07:00
documentation
PRO PIPE
is_lateral_inspection
false