Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 19, 2017, 09:34 AM
  • 02 0625_02 2181_19052017_023505.mp4

Date
05/19/2017
W/O
618894
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00258
PipeID
P03175
Time
2:34 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4557
Sewer Name
02 EAST COMPTON BOULEVARD EXTENSION TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
33
Purpose
Routine Assessment
Project
WO_618894_TV02057_MAY2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0625
Downstream MH
02 2181
Dir. of Survey
Downstream
Length Surveyed
308.2 ft.
Total Length
308.2 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
180
O&M Index
2
O&M Quick
2K00
O&M Rating
122
Overall Index
3
Overall Quick
Overall Rating
302
Pipe schematic from manhole 02 0625 to 02 2181
MH: 02 0625MH: 02 2181downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 06252 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start39.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"91.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"142.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"203 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"251 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"291.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"307.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish307.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish308.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE308.2 ft. AMH - Downstream Manhole, Survey Ends - 02 2181

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
308.2MGOCOCKROACHES IN MANHOLE
0MWM
203TFC
307.2CM
91.3TFC
0MWL
291.5TFC
308.2AMH02 2181
5.6CM
251TFC
307.2DAGS
0AMH02 0625
39.1TFA
2DAGS
142.9TFA

Properties (6)

additional_info
SC345233
custom_field_two
3
customer
LACSD
datetime
2017-05-19T02:34:36-07:00
documentation
PRO PIPE
is_lateral_inspection
false