Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 31, 2016, 06:14 AM
  • 01 0188_01 0187_30082016_231508.mpg

Date
08/30/2016
W/O
585995
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00202
PipeID
P01229
Time
11:14 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3576
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_585995_TV01012_AUG2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0188
Downstream MH
01 0187
Dir. of Survey
Downstream
Length Surveyed
120.8 ft.
Total Length
120.8 ft.
Structural Index
3
Structural Quick
4131
Structural Rating
9
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 01 0188 to 01 0187
MH: 01 0188MH: 01 0187downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 01880 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK0 ft. MWL - Water Level, 20 %of cross sectional area3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start11.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start11.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish13.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"40.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"55.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish55.7 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start61 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"75.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"85.5 ft. RFJ - Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YES108.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"114.9 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish120.8 ft. AMH - Downstream Manhole, Survey Ends - 01 0187120.8 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK

Observation photos (4)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    11.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    55.7 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YES

    85.5 ft. - Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
13.5TFC
120.8AMH01 0187
55.7CM
85.5RFJ
0MWM
11.9CM
0AMH01 0188
55.7FM
11.9CL
3CL
108.8TFC
120.8MGOLATERAL AT MH 3 OCLOCK
114.9FM
40.4TFC
0MGOLATERAL AT MH 9 OCLOCK
75.9TFC
0MWL
61TF

Properties (6)

additional_info
SC306166
custom_field_two
2
customer
LACSD
datetime
2016-08-30T23:14:10-07:00
documentation
PROPIPE
is_lateral_inspection
false