Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 31, 2016, 08:06 AM
  • 01 0181_01 0180_31082016_010704.mpg

Date
08/31/2016
W/O
585995
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00202
PipeID
P01221
Time
1:06 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3576
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_585995_TV01012_AUG2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0181
Downstream MH
01 0180
Dir. of Survey
Downstream
Length Surveyed
163.3 ft.
Total Length
163.3 ft.
Structural Index
3
Structural Quick
3321
Structural Rating
11
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
11
Pipe schematic from manhole 01 0181 to 01 0180
MH: 01 0181MH: 01 0180downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 01810 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area26.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"29 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"52.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"53.6 ft. CM - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES55 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"75.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"78.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"97.2 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES102 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"105.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"118.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"120.5 ft. CS - Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES134.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"136.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"158.6 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES163.3 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK CAPPED163.3 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK CAPPED163.3 ft. AMH - Downstream Manhole, Survey Ends - 01 0180

Observation photos (5)

  • Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

    53.6 ft. - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    97.2 ft. - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    118.6 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES

    120.5 ft. - Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    158.6 ft. - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

Observations (23)

DistanceCodeObservation
118.6TB
136.9TFC
97.2CM
0AMH01 0181
0MGOLATERAL AT MH 3 OCLOCK
75.8TFC
0MGOLATERAL AT MH 9 OCLOCK
163.3MGOLATERAL AT MH 9 OCLOCK CAPPED
78.3TF
163.3MGOLATERAL AT MH 3 OCLOCK CAPPED
55TF
29TFC
0MWL
52.5TF
105.2TFC
53.6CM
26.5TFC
102TFC
134.6TF
163.3AMH01 0180
120.5CS
0MWM
158.6CM

Properties (6)

additional_info
SC306166
custom_field_two
3
customer
LACSD
datetime
2016-08-31T01:06:26-07:00
documentation
PROPIPE
is_lateral_inspection
false