Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 15, 2016, 11:21 AM
  • B 1069_B 1068 _08152016_044258.mp4

Date
08/15/2016
W/O
585984
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00923
PipeID
P23035
Time
4:21 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3682
Sewer Name
B JOINT OUTFALL B - UNIT 1C REPLACEMENT
City
MONTEBELLO, CA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
19
Purpose
Routine Assessment
Project
WO_585984_TV02129_AUG2016
Sewer Type
Gravity
Material
RGRCP-PTL
Shape
Circular
Height
78 in.
Width
78 in.
Upstream MH
B 1069
Downstream MH
B 1068
Dir. of Survey
Downstream
Length Surveyed
320.1 ft.
Total Length
320.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole B 1069 to B 1068
MH: B 1069MH: B 1068downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 10690 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start319.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish320.1 ft. MSA - Survey Abandoned - DUE TO BOAT NOT MOVING ANY FURTHER BOAT HAS STOPPED

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (6)

DistanceCodeObservation
319.8DAGS
0AMHB 1069
0MWM
320.1MSADUE TO BOAT NOT MOVING ANY FURTHER BOAT HAS STOPPED
0MWL
0DAGS

Properties (6)

additional_info
SC306012
custom_field_two
5
customer
LACSD
datetime
2016-08-15T04:21:00-07:00
documentation
PRO-PIPE
is_lateral_inspection
false