Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 25, 2016, 10:59 AM
  • B 1040_B 1039 _08252016_040412.mp4

Date
08/25/2016
W/O
585984
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00923
PipeID
P22483
Time
3:59 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3691
Sewer Name
B JOINT OUTFALL B - UNIT 1C REPLACEMENT
City
DOWNEY, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
29
Purpose
Routine Assessment
Project
WO_585984_TV02129_AUG2016
Sewer Type
Siphon
Material
RGRCP-PTL
Shape
Circular
Height
66 in.
Width
66 in.
Upstream MH
B 1039
Downstream MH
B 1040
Dir. of Survey
Upstream
Length Surveyed
2 ft.
Total Length
2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
4
O&M Quick
5121
O&M Rating
7
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole B 1039 to B 1040
MH: B 1039MH: B 1040upstream0 ft. MSA - Survey Abandoned - DUE TO SIPHON0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES0 ft. MGO - General Observation - VIEW OF THE UPLEG OF THE DOWSTREAM MH2 ft. AMH - Downstream Manhole, Survey Begins - B 10392 ft. MWM - Water Mark, 100 %of cross sectional area2 ft. MWL - Water Level, 95 %of cross sectional area

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES

  • General Observation - VIEW OF THE UPLEG OF THE DOWSTREAM MH

    2 ft. - General Observation - VIEW OF THE UPLEG OF THE DOWSTREAM MH

Observations (6)

DistanceCodeObservation
0AMHB 1039
2MSADUE TO SIPHON
0MWM
0MWL
2DAGS
2MGOVIEW OF THE UPLEG OF THE DOWSTREAM MH

Properties (7)

additional_info
SC306021
custom_field_two
4
customer
LACSD
datetime
2016-08-25T03:59:39-07:00
documentation
PRO-PIPE
is_lateral_inspection
false
year_laid
36451