Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 7, 2016, 06:21 AM
  • 01 1005A_01 1005_06092016_232209.mp4

Date
09/06/2016
W/O
585982
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00221
PipeID
P01851
Time
11:21 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3580
Sewer Name
01 VERNON EXTENSION TRUNK
City
VERNON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Routine Assessment
Project
WO_585982_TV01065_AUG2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
01 1005A
Downstream MH
01 1005
Dir. of Survey
Downstream
Length Surveyed
203.6 ft.
Total Length
203.6 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole 01 1005A to 01 1005
MH: 01 1005AMH: 01 1005downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 1005A0 ft. MWM - Water Mark, 15 %of cross sectional area64.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start74.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"77.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"79.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish147.6 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start175.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"177.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"203.6 ft. AMH - Downstream Manhole, Survey Ends - 01 1005203.6 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (2)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    64.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Deposits Settled Other,  10 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    147.6 ft. - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0MWL
175.2TFC
203.6AMH01 1005
0AMH01 1005A
77.1TFC
203.6DSZ
147.6DSZ
177.5TFC
79.7CL
0MWM
64.1CL
74.5TF

Properties (6)

additional_info
SC306170
custom_field_two
4
customer
LACSD
datetime
2016-09-06T23:21:59-07:00
documentation
PROPIPE
is_lateral_inspection
false