Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 31, 2017, 07:26 AM
  • 02 0388_02 0387A_5312017_004439.mp4

Date
05/31/2017
W/O
0635406
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00250
PipeID
P02707
Time
12:26 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0541
Sewer Name
02 DOWNEY AVENUE EXTENSION TRUNK
City
PARAMOUNT
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Capital Improvement Program Assesment
Project
20170530MDM_DOWNEY_AVENUE_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 0388
Downstream MH
02 0387A
Dir. of Survey
Downstream
Length Surveyed
313.7 ft.
Total Length
313.7 ft.
Structural Index
2
Structural Quick
352A
Structural Rating
37
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
39
Pipe schematic from manhole 02 0388 to 02 0387A
MH: 02 0388MH: 02 0387Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 12:35AM0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area3 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SLIGHT3 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SLIGHT8 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - HAIRLINE11.4 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - H11.4 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SL15.5 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL19.5 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL23.7 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H23.7 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL27.2 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H28.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES28.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active30.5 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H30.5 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES - H34 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS34 ft. MGO - General Observation - 15" VCP34 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS34 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS34 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS60.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open87 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open89.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active182.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped185.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open225.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open228.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped263.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped266.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active301.2 ft. MWM - Water Mark, 40 %of cross sectional area313.4 ft. FL - Fracture Longitudinal, at 08 TO 4 o'clock, within 8 inches of joint: YES, Finish - 20%HAIRLINE AT JOINTS313.4 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 70% SLIGHT AT JOINTS313.4 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active313.4 ft. FL - Fracture Longitudinal, at 08 TO 4 o'clock, within 8 inches of joint: YES, Finish - 20% SLIGHT AT JOINTS313.4 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 60% HAIRLINE AT JOINTS313.7 ft. AMH - Downstream Manhole, Survey Ends - 1:20AM

Observation photos (1)

  • General Observation - 15" VCP

    34 ft. - General Observation - 15" VCP

Observations (38)

DistanceCodeObservation
87TFOpen
34FCHAIRLINE AT JOINTS
30.5FLH
23.7FCH
34MGO15" VCP
23.7FCSL
89.9TFActive
3FCSLIGHT
28.5DAGS
185.7TFOpen
313.7AMH1:20AM
0AMH12:35AM
11.4FCH
27.2FCH
19.5FCSL
0MWM
313.4FL20%HAIRLINE AT JOINTS
34FCSLIGHT AT JOINTS
34FLSLIGHT AT JOINTS
225.1TFOpen
11.4FLSL
34FLHAIRLINE AT JOINTS
313.4FC70% SLIGHT AT JOINTS
28.5TFActive
8FCHAIRLINE
266.8TFActive
60.1TFOpen
3FCSLIGHT
301.2MWM
313.4MGOConn. @ Mh, 9 O' Clock. Active
15.5FCSL
0MWL
182.5TFCCapped
228.3TFCCapped
30.5FLH
313.4FL20% SLIGHT AT JOINTS
263.7TFCCapped
313.4FC60% HAIRLINE AT JOINTS

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2017-05-31T00:26:06-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false