Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 30, 2017, 07:14 PM
  • C 0174_C 0173_5302017_122254.mp4

Date
05/30/2017
W/O
0635652
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00130
PipeID
P09698
Time
12:14 PM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7419
Sewer Name
C JOINT OUTFALL C - UNIT 5C
City
LONG BEACH
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
253.81
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20170530DF_JOINT_OUTFALL_C_UNIT_5C
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
C 0174
Downstream MH
C 0173
Dir. of Survey
Downstream
Length Surveyed
257.4 ft.
Total Length
257.4 ft.
Structural Index
4
Structural Quick
5531
Structural Rating
32
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
4
Overall Quick
Overall Rating
34
Pipe schematic from manhole C 0174 to C 0173
MH: C 0174MH: C 0173downstream0 ft. AMH - Upstream Manhole, Survey Begins - 12:16 PM0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start25.4 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start36.4 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Finish64.4 ft. SRV - Surface Reinforcement Visible, from 10 to 04 o'clock, within 8 inches of joint: YES74.9 ft. MGP - General Photograph - REINFORCEMENT74.9 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start81.4 ft. MGO - General Observation - AGGREGATE119.8 ft. MGP - General Photograph - AGGREGATE/SPALLING141 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"144.9 ft. MGP - General Photograph - SPALLING169 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES201.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 11 o'clock, , within 8 inches of joint: YES202.7 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES250.4 ft. SRV - Surface Reinforcement Visible, from 02 to 04 o'clock, within 8 inches of joint: YES254.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish254.6 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish254.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish257.4 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active257.4 ft. AMH - Downstream Manhole, Survey Ends - 12:57 PM257.4 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN

Observation photos (12)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start

    25.4 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 10 to 04 o'clock, within 8 inches of joint: YES

    64.4 ft. - Surface Reinforcement Visible, from 10 to 04 o'clock, within 8 inches of joint: YES

  • General Photograph - REINFORCEMENT

    74.9 ft. - General Photograph - REINFORCEMENT

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    74.9 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - AGGREGATE

    81.4 ft. - General Observation - AGGREGATE

  • General Photograph - AGGREGATE/SPALLING

    119.8 ft. - General Photograph - AGGREGATE/SPALLING

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

    169 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 11 o'clock,  , within 8 inches of joint: YES

    201.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 11 o'clock, , within 8 inches of joint: YES

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES

    202.7 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 02 to 04 o'clock, within 8 inches of joint: YES

    250.4 ft. - Surface Reinforcement Visible, from 02 to 04 o'clock, within 8 inches of joint: YES

Observations (27)

DistanceCodeObservation
74.9MGPREINFORCEMENT
0AMH12:16 PM
74.9SRV
254.6SSS
0MGOROACHES @ MH
2SAV
202.7SRV
81.4MGOAGGREGATE
257.4MGOConn. @ Mh, 3 O' Clock. Active
0MWM
25.4SRV
201.6DAGS
119.8MGPAGGREGATE/SPALLING
254.6SRV
257.4AMH12:57 PM
0MWL
0MGOConn. @ Mh, 3 O' Clock. Active
144.9MGPSPALLING
141TFA
257.4MGOConn. @ Mh, 9 O' Clock. OPEN
64.4SRV
254.6SAV
250.4SRV
36.4SRV
2SSS
169SSS
0MGOConn. @ Mh, 9 O' Clock. Active

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2017-05-30T12:14:01-07:00
documentation
FRANKLIN, IGNACIO, BRAR
is_lateral_inspection
false