Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 30, 2017, 04:13 PM
  • C 0173_C 0172_5302017_095521.mp4

Date
05/30/2017
W/O
0635652
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00130
PipeID
P09697
Time
9:13 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7419
Sewer Name
C JOINT OUTFALL C - UNIT 5C
City
LONG BEACH
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
253.81
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20170530DF_JOINT_OUTFALL_C_UNIT_5C
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
C 0172
Downstream MH
C 0173
Dir. of Survey
Upstream
Length Surveyed
253.1 ft.
Total Length
253.1 ft.
Structural Index
4
Structural Quick
5631
Structural Rating
35
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
4
Overall Quick
Overall Rating
37
Pipe schematic from manhole C 0172 to C 0173
MH: C 0172MH: C 0173upstream0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Ends - 11:40 AM0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish41.1 ft. MGP - General Photograph - REINFORCEMENT41.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES81.6 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES103.7 ft. MGO - General Observation - AGGREGATE121 ft. SRV - Surface Reinforcement Visible, from 01 to 04 o'clock, within 8 inches of joint: YES140.8 ft. OBM - Obstacles Pipe Material, 5 %of cross sectional area, from 01 to 02 o'clock - 2"140.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"174.9 ft. SRC - Surface Reinforcement Corroded, from 09 to 11 o'clock, within 8 inches of joint: YES193.1 ft. SRV - Surface Reinforcement Visible, from 12 to 04 o'clock, within 8 inches of joint: YES251.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start251.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start251.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start253 ft. MGO - General Observation - ROACHES @ MH253 ft. MWL - Water Level, 30 %of cross sectional area253 ft. MWM - Water Mark, 35 %of cross sectional area253.1 ft. AMH - Downstream Manhole, Survey Begins - 9:24 AM

Observation photos (11)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 12 to 04 o'clock, within 8 inches of joint: YES

    60 ft. - Surface Reinforcement Visible, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Corroded, from 09 to 11 o'clock, within 8 inches of joint: YES

    78.2 ft. - Surface Reinforcement Corroded, from 09 to 11 o'clock, within 8 inches of joint: YES

  • Obstacles Pipe Material, 5 %of cross sectional area, from 01 to 02 o'clock - 2"

    112.3 ft. - Obstacles Pipe Material, 5 %of cross sectional area, from 01 to 02 o'clock - 2"

  • Surface Reinforcement Visible, from 01 to 04 o'clock, within 8 inches of joint: YES

    132.1 ft. - Surface Reinforcement Visible, from 01 to 04 o'clock, within 8 inches of joint: YES

  • General Observation - AGGREGATE

    149.4 ft. - General Observation - AGGREGATE

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    171.5 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

  • General Photograph - REINFORCEMENT

    212 ft. - General Photograph - REINFORCEMENT

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    212 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
132.1SRV
112.3OBM2"
0AMH9:24 AM
112.3TFA
2SAV
253SSS
0.1MGOROACHES @ MH
253.1MGOConn. @ Mh, 9 O' Clock. Active
253.1AMH11:40 AM
171.5SRV
60SRV
212MGPREINFORCEMENT
2SRV
149.4MGOAGGREGATE
253SAV
2SSS
0.1MWL
0.1MWM
253.1MGOConn. @ Mh, 3 O' Clock. Active
78.2SRC
253SRV
212SRV

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2017-05-30T09:13:05-07:00
documentation
FRANKLIN, IGNACIO, BRAR
is_lateral_inspection
false