Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 26, 2017, 08:28 AM
  • 01 1230_01 1229_5262017_013243.mp4

Date
05/26/2017
W/O
0635395
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00217
PipeID
P02054
Time
1:28 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0538
Sewer Name
01 SANTA FE AVENUE TRUNK
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Routine Assessment
Project
20170526MDM_SANTA_FE_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
01 1230
Downstream MH
01 1229
Dir. of Survey
Downstream
Length Surveyed
190.5 ft.
Total Length
190.5 ft.
Structural Index
2
Structural Quick
352G
Structural Rating
99
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
99
Pipe schematic from manhole 01 1230 to 01 1229
MH: 01 1230MH: 01 1229downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:30AM0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTCHED5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETE SEVERE AGG ATTCHED5 ft. MMC - Material Change, Vitrified clay pipe - STARTS5 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - HAIRLINE8 ft. MGO - General Observation - 15" VCP16.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE24.2 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H29.3 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H29.3 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H31.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H31.8 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H37.3 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H39.4 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINES AT JOINTS39.4 ft. FL - Fracture Longitudinal, at 08 TO 4 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS42.1 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - SL47.2 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL47.2 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL52.2 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL57.1 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL57.1 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL59.6 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL64.6 ft. FC - Fracture Circumferential, from 08 to 01 o'clock, within 8 inches of joint: YES - SL67.5 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL69.8 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL72.3 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL74.8 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL77.2 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL77.2 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL79.8 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL82.3 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL85 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL85 ft. MWM - Water Mark, 40 %of cross sectional area85 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL90 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL102.8 ft. FC - Fracture Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES - SL103.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open113 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL113 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL115.3 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL117.8 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL127.7 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL133 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL145.7 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL145.7 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL148 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL150.9 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL150.9 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL155.9 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL160.9 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL160.9 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - DL170.7 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL186.7 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL190 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 60% HAIRLINE AT JOINTS190 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active190 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 20% HAIRLINE AT JOINTS190.5 ft. AMH - Downstream Manhole, Survey Ends - 2:20AM

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTCHED

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTCHED

  • General Observation - 15" VCP

    8 ft. - General Observation - 15" VCP

Observations (60)

DistanceCodeObservation
5SSSPEELING CONCRETE SEVERE AGG ATTCHED
0MWM
113FCSL
47.2FCSL
145.7FCSL
79.8FCSL
69.8FCSL
133FLSL
190FC60% HAIRLINE AT JOINTS
72.3FCSL
85FCSL
102.8FCSL
29.3FCH
127.7FCSL
5MMCSTARTS
31.8FLH
77.2FCSL
190MGOConn. @ Mh, 9 O' Clock. Active
85MWM
31.8FLH
145.7FCSL
82.3FCSL
74.8FCSL
67.5FCSL
150.9FCSL
42.1FCSL
2SSSPEELING CONCRETE SEVERE AGG ATTCHED
155.9FCSL
190.5AMH2:20AM
148FCSL
52.2FCSL
39.4FCHAIRLINES AT JOINTS
8MGO15" VCP
24.2FCH
16.8FLHAIRLINE
85FCSL
59.6FCSL
5FCHAIRLINE
115.3FCSL
190FL20% HAIRLINE AT JOINTS
57.1FCSL
117.8FCSL
39.4FLHAIRLINE AT JOINTS
64.6FCSL
160.9FCSL
150.9FCSL
0AMH1:30AM
90FCSL
57.1FCSL
103.7TFOpen
37.3FCH
29.3FCH
47.2FCSL
160.9FCDL
170.7FCSL
77.2FCSL
0MGOConn. @ Mh, 9 O' Clock. Active
186.7FCSL
0MWL
113FCSL

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2017-05-26T01:28:23-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false